How to Guide

"
INTRODUCTION
Thank you for choosing BRK Brands, Inc. for your Smoke and Carbon
Monoxide Alarm needs. You have purchased a state-of-the-art Smoke &
CO Alarm designed to provide you with early warning of a fire or Carbon
Monoxide. 464+2,.4)615'*,&4
0 3466-+.356%3531&46-3 15+21356!*+. ( One alarm protects
against two deadly household threats.
%3)26!'',.+246-+.356%3531&46045)3.6Advanced electroch
emical
CO sensor technology.
"524**1$4526045)15$6#4'53*3$ designed to help reduce unwanted or
nuisance alarms.
0 +.26"524.'3554'2 can be interconnected to BRK Smoke Alarms.
One interconnect wire carries both smoke and CO alarm signals.
015$*46,22356#4)201*45'4 eliminates confusion. Depending on what
mode the alarm is in, pushing the button provides different functions
such as testing the alarm, silencin
g the alarm, re-testing the alarm
when in silence and clearing the Latching feature.
#3601*45'464+2,.4)(6Temporarily silence low battery chirp for up to
eight hours before replacing low battery or silence an unwanted alarm
for several minutes.
#36+2'15$64+2,.4)( Alarm Latch: Easily identifies initiating alarm
even after alarm condition has subsided. Low Battery Latch: Identifies
which unit is in low
battery condition.
4.4'26%3,5260)24 includes a gasketless base for easy installation
and a new mounting bracket that keeps the alarm secure over a wide
rotation range to allow for perfect alignment.
5&63614601$5+*( Provides audible and visual confirmation alarm
needs to be replaced.
As compared to other sensing technologies
© 2014 BRK Brands, Inc. All rights reserved.
Distributed by BRK Brands, I
nc.
3901 Liberty Street Road, Aurora, IL 60504-8122
Consumer Affairs: (800) 323-9005
www.brkelectronics.com www.firstalert.com
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking
materials properly. Never smoke in bed. 2) Keep matches or lighters
away from children; 3) Store flammable materials in proper containers;
4) Keep electrical appliances in good condition and don’t overload elec-
trical circuits; 5) Keep stoves, barbecue grills, fireplaces and chimneys
grease- and debris-free; 6) Never leave anything cooking on the stove
unattended; 7) Keep portable heaters and open flames, like candles,
away from flammable materials; 8) Don’t let rubbish accumulate.
Keep alarms clean, and test them weekly. Replace alarms immediately
if they are not working properly. Sm
oke Alarms that do not work cannot
alert you to a fire. Keep at least one working fire extinguisher on every
floor, and an additional one in the kitchen. Have fire escape ladders or
other reliable means of escape from an upper floor in case stairs are
blocked.
BASIC SAFETY INFORMATION
NNN,IH:MJF+NIJHGH:F+NIH@N9IBLGKHFNIEMJLN=KBNLKNGD>KJLIHLN
K>MJILGH:NGHFLJBALGKHFNKJNLKN>KLMHLGIEE=NCIIJ@KBFNFGLBILGKHF;N
%I=NF>MAGIENILLMHLGKHNLKNLCMFMNGLMDF;
NNN3CGFN6DK2M(97N?EIJDNGFNI>>JK-M@N<KJNBFMNGHNFGH:EM!<IDGE=
JMFG@MHAMF;N.LNGFN*73N@MFG:HM@N<KJNDIJGHMNKJN)NBFM;
NNN
3CGFNAKD5GHILGKHN6DK2M(9IJ5KHN$KHK G@MN?EIJDNCIFNL8K
FM>IJILMNIEIJDF;N3CMN97N?EIJDNGFNHKLN@MFG:HM@NLKN@MLMALN<GJMN
KJNIH=NKLCMJN:IF;N.LN8GEENKHE=NGH@GAILMNLCMN>JMFMHAMNK<NAIJ5KH
DKHK G@MN:IFNILNLCMNFMHFKJ;N9IJ5KHNDKHK G@MN:IFNDI=N5M
>JMFMHLNGHNKLCMJNIJMIF;N3CMN6DK2MN?EIJDN8GEENKHE=NGH@GAILMNLCM
>JMFMHAMNK<NFDK2MNLCILNJMIACMFNLCMNFMHFKJ;N3CMN6DK2MN?EIJD
GFNHKLN@MFG:HM@NLKNFMHFMN:IF+NCMILNKJN<EIDMF;
?EEN#)
IH@N
&GJFLN?EMJL
6DK2MN?EIJDFNAKH<KJDNLKNJM:BEILKJ=
JMBGJMDMHLF+NGHAEB@GH:N0"NIH@NIJMN@MFG:HM@NLKN@MLMALN>IJLGAEMF
K<NAKD5BFLGKH;N6DK2MN>IJLGAEMFNK<N-IJ=GH:NHBD5MJNIH@NFGMNIJMN
>JK@BAM@NGHNIEEN<GJMF;
Ionization technology is generally more sensitive than photo-
electric technology at detecting small particles, which tend to be
produced in greater amounts by flaming fires, which consume
combustible materials rapidly and spread quickly. Sources of these
fires may include paper burning in a wastebasket, or a grease fire in
the kitchen.
Photoelectric technology is generally more sensitive than ionization
technology at detecting large particles, which tend to be produced
in greater amounts by smoldering fires, which may smolder for
hours before bursting into flame. Sources of these fires may inc
lude
cigarettes burning in couches or bedding.
&KJNDI GDBDN>JKLMALGKH+NBFMN5KLCNL=>MFNK<N6DK2MN?EIJDFNKH
MIACNEM-MENIH@NGHNM-MJ=N5M@JKKDNK<N=KBJNCKDM;
10193).9?0N6'79N'??),;N3BJHNK<<NLCMN>K8MJNLKNLCMNIJMI
8CMJMNLCMN6DK2M(97N?EIJDNGFNGHFLIEEM@N5M<KJMNJMDK-GH:NGLN<JKD
LCMNDKBHLGH:N5JIA2ML;N&IGEBJMNLKNLBJHNK<<NLCMN>K8MJN<GJFLNDI=
JMFBELNGHNFMJGKBFNMEMALJGAIENFCKA2+NGHBJ=NKJN@MILC;
3CGFNBHGLN8GEENHKLNIEMJLNCMIJGH:NGD>IGJM@NJMFG@MHLF;N.LNGFN
JMAKDDMH@M@NLCILN=KBNGHFLIEENF>MAGIENBHGLFN8CGACNBFMN@M-GAMF
EG2MN<EIFCGH:NFLJK5MNEG:CLFNLKNIEMJLNCMIJGH:NGD>IGJM@NJMFG@MHLF;
.HFLIEEILGKHNK<NLCGFNBHGLNDBFLNAKH<KJDNLKNLCMNMEMALJGAIENAK@MF
GHN=KBJNIJMIN?JLGAEMFN"NIH@N;N#NK<N*&%?NN*19+
*&%?N+N*&%?N""N.99N6#9N6#99.N#9N.9#7N
*#9N#79?N73&,9N9?#7+NIH@NIH=NKLCMJNEKAIENKJN5BGE@GH:
AK@MFNLCILNDI=NI>>E=;NGJGH:NIH@NGHFLIEEILGKHNDBFLN5MN
>MJ<KJDM@N5=NINEGAMHFM@NMEMALJGAGIH;N&IGEBJMNLKN<KEEK8NLCMFM
:BG@MEGHMFNDI=NJMFBELNGHNGHBJ=NKJN>JK>MJL=N@I
DI:M;
3CGFNBHGLNDBFLN5MN>K8MJM@N5=NIN!CKBJ+N"N?9N>BJMNFGHM
8I-MNN'NAGJABGL;N#MNFBJMNLCMNAGJABGLNAIHHKLN5MNLBJHM@NK<<N
5=NINF8GLAC+N@GDDMJ+NKJN:JKBH@N<IBELNAGJABGLNGHLMJJB>LMJ;
&IGEBJMNLKNAKHHMALNLCGFNBHGLNLKNIN!CKBJNAGJABGLNDI=N>JM-MHLNGL
<JKDN>JK-G@GH:NAKHFLIHLN>JKLMALGKH;N
HGLNDI=N5MNAKHHMALM@NLK
IHNIJAN<IBELNAGJABGLNGHLMJJB>LMJ;
3CGFN6DK2M(97N?EIJDNDBFLNCI-MN?9NKJN5ILLMJ=N>K8MJNLKN
K>MJILM;N.<N?9N>K8MJN<IGEFNIH@NLCMN5ILLMJ=NGFN@MI@NKJNDGFFGH:+
LCMNIEIJDNAIHHKLNK>MJILM;
*M-MJN@GFAKHHMALNLCMN>K8MJN<JKDNIHN?9N>K8MJM@NBHGLNLKN
FLK>NIHNBH8IHLM@NIEIJD;N,KGH:NFKN8GEEN@GFI5EMNLCMNBHGLNIH@
JMDK-MN=KBJN>JKLMALGKH;N.HNLCMNAIFMNK<NINLJBMNBH8IHLM@N
IEIJD+NBFMNLCMN6GEMHAMN&MILBJMNG<NMBG>>M@+NK>MHNIN8GH@K8
KJN<IHNLCMNFDK2MNI8I=N<JKDNLCMNBHGL;N3CMNIEIJDN8GEENJMFML
IBLKDILGAIEE=N8CMHNGLNJMLBJHFNLKNHKJDIENK>MJILGKH;N*M-MJ
JMDK-MNLCMN5ILLMJGMFN<JKDNIN5ILLMJ=NK>MJILM@NBHGLNLKNFLK>NIH
BH8IHLM@NIEIJDNAIBFM@N5=NAKK2GH:NFDK2M+NMLA;;N.HFLMI@
K>MHNIN8GH@K8NKJN<IHNLCMNFDK2MNI8I=N<JKDNLCMNBHGL;N3CM
IEIJDN8GEENJMFMLNIBLKDILGAIEE=;
INSTALLATION
WHERE TO INSTALL THIS ALARM
$GHGDBDNAK-MJI:MN<KJN6DK2MN?EIJDF, as recommended by the
National Fire Protection Association (NFPA), is one Smoke Alarm on
every floor, in every sleeping area, and in every bedroom (See
“Regulatory Information For Smoke Alarms” for details on the NFPA
recommendations).
&KJN97N?EIJDF+ the National Fire Protection Association (NFPA)
recommends that a CO Alarm shoul
d be centrally located outside of
each separate sleeping area in the immediate vicinity of the bedrooms.
For added protection, install additional CO Alarms in each separate
bedroom, and on every level of your home.
.HN:MHMJIE+NGHFLIEENAKD5GHILGKHN6DK2MNIH@N9IJ5KHN$KHK G@M
?EIJDF/
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep wit
h the door partly
or completely closed.
In the hall near every sleeping area. If your home has multiple
sleeping areas, install a unit in each. If a hall is more than 40 feet
(12 meters) long, install a unit at each end.
At the top of first-to-second floor stairs.
At the bottom of the basement stairs.
For additional coverage, install Alarms in all rooms, halls, and storage
areas, where temperatures
normally remain between 40˚ F and
100˚ F (4.4˚ C and 37.8˚ C).
)MAKDDMH@M@N%EIAMDMHL
When installing on the wall, the top edge of Smoke Alarms should
be placed between 4 inches (102 mm) and 12 inches (305 mm)
from the wall/ceiling line.
When installing on the ceiling, place the alarm as close to the
center as possible.
In either case, install at least 4 inches (102 mm) from where the
wall and ceiling
meet. See “Avoiding Dead Air Spaces” for more
information.
*731/ For any location, make sure no door or other obstruction could
keep carbon monoxide or smoke from reaching the Alarm.
"5)2+**15$60 34-/6!*+. )6156%31*463 4)
For minimum security install one Smoke/CO Alarm as close to each
sleeping area as possible. For more security, put one unit in each room.
Many older mobile homes (especially those b
uilt before 1978) have little
or no insulation. If your mobile home is not well insulated, or if you are
unsure of the amount of insulation, it is important to install units on
inside walls only.
WHERE THIS ALARM SHOULD NOT BE INSTALLED
,KN*73NEKAILMNLCGFN6DK2M(97N?EIJD/
In garages, kitchens, furnace rooms, crawl spaces and unfinished
attics. Avoid extremely dusty, dirty or greasy areas.
Where combustio
n particles are produced. Combustion particles
form when something burns. Areas to avoid include poorly ventilated
kitchens, garages, and furnace rooms. Keep units at least 20 feet
(6 meters) from the sources of combustion particles (stove, furnace,
water heater, space heater) if possible. In areas where a 20-foot
(6 meter) distance is not possible in modular, mobile, or smaller
homes, for example it is recommended the Smoke/CO Alarm be
placed as far from these fuel-burning sources as possible. The
placement recommendations are intended to keep these Alarms at
a reasonable distance from a fuel-burning source, and thus reduce
“unwanted” alarms. Unwanted alarms can occur if a Smoke/CO
Alarm is placed directly next to a fuel-burning source. Ventilate
these areas as much as possible.
Within 5 feet
(1.5 meters) of any cooking appliance. In air streams
near kitchens. Air currents can draw cooking smoke into the smoke
sensor and cause unwanted alarms.
In extremely humid areas. This Alarm should be at least 10 feet
(3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher,
laundry room, utility room, or other source of high humidity.
In direct sunlight.
In turbulent air, like near ceilin
g fans or open windows. Blowing air
may prevent CO or smoke from reaching the sensors.
In areas where temperature is colder than 40˚ F (4.4˚ C) or hotter
than 100˚ F (37.8˚ C). These areas include non-airconditioned crawl
spaces, unfinished attics, uninsulated or poorly insulated ceilings,
porches, and garages.
In insect infested areas. Insects can clog the openings to the
sensing chamber.
Less than 1
2 inches (305 mm) away from fluorescent lights.
Electrical “noise” can interfere with the sensor.
In “dead air” spaces. See “Avoiding Dead Air Spaces”.
?7.,.*N,1?,N?.)N6%?916
“Dead air” spaces may prevent smoke from reaching the Smoke/CO
Alarm. To avoid dead air spaces, follow installation recommendations
below.
7HNAMGEGH:F+ install Smoke/CO Alarms as close to the center of the
ceiling as possible. If this is not possible, install the Smoke/CO Alarm
at least 4 inches (102 mm) from the wall or corner.
&KJN8IEENDKBHLGH: (if allowed by building codes), t
he top edge of
Smoke/CO Alarms should be placed between 4 inches (102 mm) and
12 inches (305 mm) from the wall/ceiling line.
7HNIN>MI2M@+N:I5EM@+NKJNAILCM@JIENAMGEGH:+ install the first Smoke/CO
Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured
horizontally. Additional Smoke/CO Alarms may be required depending
on the length, angle, etc. of the ceiling's slope. Refer to NFPA 72 for
de
tails on requirements for sloped or peaked ceilings.
-35215,4&(((
BEFORE YOU BEGIN INSTALLATION
This unit is designed to be mounted on any standard wiring junction
box up to a 4-inch (10 cm) size, on either the ceiling or wall. Read
“Where to Install This Alarm” and “Where This Alarm Should Not Be
Installed ” before you begin installation.
N$I2MNFBJMNLCMNIEIJDNGFNHKLNJMAMG-GH:NM AMFFG-ME=NHKGF=N>K8MJ;
1 ID>EMFNK<NHKGF=N>K8MJNAKBE@N5MNDIKJNI>>EGIHAMFNKHNLCM
FIDMNAGJABGL+N>K8MJN<JKDNIN:MHMJILKJNKJNFKEIJN>K8MJ+NEG:CLN@GD!
DMJNKHNLCMNFIDMNAGJABGLNKJNDKBHLM@NHMIJN<EBKJMFAMHLNEG:CLGH:;
1 AMFFG-ME=NHKGF=N>K8MJNDI=NAIBFMN@IDI:MNLKN=KBJN?EIJD;
Find the pair of self-adhesive labels included with this Smoke/CO Alarm.
• On each label write in the phone number of your emergency
responder (like 911) and a qualified appliance technician.
• Place one label near the Smoke/CO Alarm,
and the other label in
the “fresh air” location you plan to go if the alarm sounds.
*731/ A qualified appliance technician is defined as “a person, firm,
corporation, or company that either in person or through a representa-
tive, is engaged in and responsible for the installation, testing, servicing,
or replacement of heating, ventilation, air conditioning (HVAC) equipment,
combustion appliances and equipment, and/or gas fireplaces or other
decorative combustion equipment.”
1 Mounting Bracket
2 Mounting Slot and Screw
3 Locking Pins (break out of
bracket)
4 Hot (Black) AC Wire
5 Neutral (White) AC Wire
6 Interconnect Wire (Orange)
7 Lever to Open Battery
Compartment
8 Swing-Out Battery
Compartment
9 Quick-Connect Power
Not Included
%?)36N7&N3'.6N6$71(97N?0?)$
3KKEFN=KBN8GEENHMM@/ Standard Flathead screwdriver, wire strippers.
10193).9?0N6'79N'??),;N3BJHNK<<N>K8MJNLKNLCMNIJMIN8CMJMN=KB
8GEENGHFLIEENLCGFNBHGLNILNLCMNAGJABGLN5JMI2MJNKJN<BFMN5K N5M<KJMN5M:GHHGH:
GHFLIEEILGKH;N&IGEBJMNLKNLBJHNK<<NLCMN>K8MJN5M<KJMNGHFLIEEILGKHNDI=
JMFBELNGHNFMJGKBFNMEMALJGAIENFCKA2+NGHBJ=NKJN@MILC;
3KNGHFLIEENLCGFNBHGL/
1. Remove the mounting bracket from the base. Position the s
crew
slots on the mounting bracket over the screws in the junction box.
Tighten the screws.
.D>JK>MJN8GJGH:NK<NLCMN>K8MJNAKHHMALKJNKJNLCMN8GJGH:NEMI@GH:NLK
LCMN>K8MJNAKHHMALKJN8GEENAIBFMN@IDI:MNLKNLCMN?EIJDNIH@NDI=NEMI@
LKNINHKH!<BHALGKHGH:N?EIJD;
2. Using wire nuts, connect the power connector to the AC power.
3. Plug the power connector into the back of the Smoke/CO Alarm.
4.
Position the base of the Smo
ke/CO Alarm over the mounting bracket
and turn. The Alarm will remain secure over a wide rotation range to
allow for perfect alignment. When wall mounting, this will allow fine-
tuning on the positioning to compensate for out of aligned wall studs
and to keep the wording level. The Alarm can be positioned over the
bracket every 120°. Rotate the Alarm until aligned properly.
63?*,N?07*1N?0?)$N7*0/
Connect the white wire on the power connector to the neutral
wire in the junction box.
Connect the black wire on the power connector to the hot wire
in the junction box.
Tuck the orange wire inside the junction box. .LNGFNBFM@N<KJN
GHLMJAKHHMALNKHE=;
.*31)97**1931,N?0?)$6N7*0/
6LJG>NK<<NI5KBLN"(NK<NLCMN>EIFLGANAKILGH:NKHNLCMNKJIH:MN
GHLMJAKHHMALN8GJMNKHNLCMN>K8MJNAKHHMALKJ;
Co
nnect the white wire on the power connector to the neutral
wire (usually white) in the junction box.
Connect the black wire on the power connector to the hot wire
(usually black) in the junction box.
Connect the orange wire on the power connector to the inter-
connect wire in the junction box. Repeat for each unit you are
interconnecting. Never connect the hot or neutral wires in the
junction box to th
e orange interconnect wire. Never cross hot
and neutral wires between interconnected Alarms.
SPECIAL REQUIREMENTS FOR INTERCONNECTED ALARMS
NNN
&IGEBJMNLKNDMMLNIH=NK<NLCMNI5K-MNJMBGJMDMHLFNAKBE@N@ID!
I:MNLCMNBHGLFNIH@NAIBFMNLCMDNLKNDIE<BHALGKH+NJMDK-GH:N=KBJN
>JKLMALGKH;
NNN?9NIH@N?9(,9N6DK2M(97N?EIJDFNAIHN5MNGHLMJAKHHMALM@;
H@MJN?9N>K8MJ+NIEENBHGLFN8GEENIEIJDN8CMHNKHMNFMHFMFNFDK2M
KJN97;NCMHN>K8MJNGFNGHLMJJB>LM@+NKHE=NLCMN?9(,9NBHGLFNGH
LCMNFMJGMFN8GEENAKHLGHBMNLKNFMH@NIH@NJMAMG-MNFG:HIEF;NN
?9N>K8MJM@N6DK2M(97N?EIJDFN8GEENHKLNK>MJILM;N6MMN6DIJL
.HLMJAKHHMALN&MILBJM;
Interconnected units can provide earlier warning of a Smoke/CO problem
than stand-alone units, especially if the problem starts in a remote area of
the dwelling. If any unit in the series senses Smoke/CO, all units will alarm.
To determine which Smoke/CO Alarm initiated an alarm, refer to the table.
,BJGH:NIHN?EIJD/
On Initiating Alarm(s) Red LED(s) flashes (flash) rapidly
On All Other Alarms Red LED is Off
?<LMJNIHN?EIJDN0ILACGH:/
On Initiating Alarm(s) Red LED(s) On for 2 seconds/Off for 2 seconds
On All Other Alarms Green LED(s) On, Red LED(s) is Off
9KD>ILG5EMN.HLMJAKHHMALM@NHGLF
Interconnect units within a single family residence only. Otherwise all
households will experience unwanted alarms when you test any unit in the
series. Interconnected units will only work if they are wired to compatible
units and all requirements are met. This unit is designed to be compatible
with: 1.)26!*4.2
6DK2MN?EIJDN$K@MEF SA4120, SA4121B, SA100B,
SA520 and 
6DK2MN?EIJDN$K@MEF 9120, 9120B, SC6120B,
SC9120B, 7010, 7010B, 7020B, SC7010B, SC7010BV, 100S, 4120,
4120B, 4120SB; 
97N?EIJDN$K@MEF CO5120BN, CO5120PDBN;

'MILN?EIJDN$K@MEFNHD6135F and HD6135FB; 
?B GEGIJ=
,M-GAMFN$K@MEF RM3 and RM4 (Relay Modules), SL177 (Strobe Light).
See www.brkelectronics.com for most current interconnect list.
.HLMJAK
HHMALM@NBHGLFNDBFLNDMMLN?00NK<NLCMN<KEEK8GH:NJMBGJMDMHLF/
• A maximum of 18 compatible BRK Electronics
®
Smoke, Heat or CO
Alarms may be interconnected. No more than 12 of the 18 can be
Smoke Alarms per NFPA 72.
• The same fuse or circuit breaker must power all interconnected units.
• The total length of wire interconnecting the units should be less
than 1000 feet (300 meters). This type of wire is comm
only available
at Hardware and Electrical Supply stores.
• All wiring must conform to all local electrical codes and NFPA 70 of
the National Electrical Code. Refer to NFPA 72, NFPA 101, and/or
your local building code for further connection requirements.
6.
Make sure the Smoke/CO Alarm is receiving AC power. Under normal
operation, the green indicator light will shine continuously.
If the green
power indicator light does not light, TURN OFF POWER TO THE
JUNCTION BOX and recheck all connections. If all connections are
correct and the green power indicator still does not light when you
restore the power, the unit should be replaced immediately.
7. ?93.?3.*
N3'1N#?331)N#?9!%
Activate the battery back-up by removing the “Pull to Activate
Battery Back-Up” tab. You do not need to open the battery
compartment and reposition the battery during installation.
,7N*73
JMDK-MNLCMN5ILLMJ=NIALG-ILGKHNLI5NBHLGEN?9N>K8MJNGFNLBJHM@NKHNLK
AKHFMJ-MN5ILLMJ=N>K8MJ;
8. 6GH:EMN6LILGKHN?EIJDF/ Test each Alarm. Press and hold the
Test/Silence button until you hear the acknowle
dge “chirp” or the
unit alarms.
.HLMJAKHHMALM@N?EIJDF/ Press and hold the Test/Silence button
until the unit alarms. All interconnected Alarms should sound. The
other Alarms sounding only tests the interconnect signal between
Alarms. It does not test each Alarm’s operation. KBNDBFLNLMFLNMIAC
?EIJDNGH@G-G@BIEE=NLKNACMA2NG<NLCMN?EIJDNGFN<BHALGKHGH:N>JK>MJE=;
If any unit in the series does not alarm during
testing, TURN OFF POWER,
REMOVE BATTERIES, and recheck connections. If it does not alarm when
you restore power, replace it immediately.
A. Unswitched 120VAC B. To Additional Alarms,
60 Hz source Maximum = 18 Alarms
1. Smoke/CO Alarm
2. Ceiling or Wall
3. Power Connector
4. Wire Nut
5. Junction Box
6. Neutral Wire (White)
7. Interconnect Wire
(Orange)
8. Hot Wire (Black)
63?*,N?07*1N?0?)$N7*0/
If you are only installing one unit, restore power to the junction box.
.*31)97**1931,N?0?)$6N7*0/
.<N=KBNIJMNGHLMJAKHHMALGH:NDBELG>EMN6DK2M(97N?EIJDF+NJM>MIL
6LM>N"!N<KJNMIACN6DK2M(97N?EIJDNGHNLCMNFMJGMF;NCMHN=KBNIJM
<GHGFCM@+NJMFLKJMN>K8MJNLKNLCMNBHALGKHN5K ;
10193).9?0N6'79N'??),;N,KNHKL
JMFLKJMN>K8MJNBHLGENIEEN
?EIJDFNIJMNAKD>EMLME=NGHFLIEEM@;N)MFLKJGH:N>K8MJN5M<KJMNGHFLIEEILGKH
HOW TO INSTALL THIS SMOKE/CO ALARM
INSTALLATION, Continued
1. Test/Silence Button: Press
and hold to activate test,
or to silence the alarm.
2. POWER Light (GREEN)/
SMOKE ALARM Light (RED)
3. CO ALARM Light (RED)
4. Battery Drawer
5. (Behind the Cover) Alarm
Horn: 85 dB audible alarm
for test, alarm, and unit
malfunction warning.
HOW YOUR SMOKE/CO ALARM WORKS
THE COVER OF YOUR SMOKE/CO ALARM
3CMNK>LGKHIENEKA2GH:N<MILBJMFNIJMN@MFG:HM@NLKN@GFAKBJI:MNBHIBLCKJGM@
JMDK-IENK<NLCMN5ILLMJ=NKJNIEIJD;N.LNGFNHKLNHMAMFFIJ=NLKNIALG-ILMNLCMNEKA2F
GHNFGH:EM!<IDGE=NCKBFMCKE@FN8CMJMNBHIBLCKJGM@N5ILLMJ=NKJNIEIJD
JMDK-IENGFNHKLNINAKHAMJH;
These Smoke/CO Alarms have two separate locking features: one locks
the battery compartment, and the other locks the Smoke/CO Alarm to the
mounting bracket. You can choose to use either feature independently, or
use them both.
3KKEFN=KBN8GEENHMM@/ • Needle-nose pliers or utility knife
• Standard/Flathead screwdriver.
USING THE OPTIONAL LOCKING FEATURES
THE BATTERY COMPARTMENT LOCK
37N079N3'1N#?331)N97$%?)3$1*3/
Do not lock the battery compartment until you have activated the battery
and tested the battery back-up.
1. Activate the battery back-up by removing
the “Pull to Activate Battery Back-Up”
tab. Push and hold the test button on the
Smoke/CO Alarm’s cover until the alarm
sounds: 4 beeps, pause, 4 beeps, pause,
3 beeps, pause, 3 beeps, pause.
.<NLCMNB
HGLN@KMFNHKLNIEIJDN@BJGH:
LMFLGH:+N,7N*73NEKA2NLCMN5ILLMJ=
AKD>IJLDMHLN.HFLIEENINHM8N5ILLMJ=
IH@NLMFLNI:IGH;N.<NGLNFLGEEN@KMFNHKL
IEIJD+NJM>EIAMNLCMN6DK2M(97
?EIJDNGDDM@GILME=;
2. Using needle-nose pliers or a utility
knife, detach one locking pin from
the mounting bracket.
3. Push the locking pin
through the black dot on
the label on the back of
the Smoke/CO Alarm.
THE MOUNTING BRACKET LOCK
37N?93.?31N3'1N#)?913N079/
1. Using needle-nose pliers, detach one locking pin from the mounting
bracket.
2. Insert the locking pin into the lock located on the base as shown in
the diagram.
3. When you attach the Smoke/CO Alarm to the mounting bracket,
the locking pin’s head will fit into a notch on the bracket.
37N,1?93.?31N3'1N#)?913N079/
10193).9?0N6'79N'??),;N3BJHNK<<NLC
MN>K8MJNLKNLCMNIJMI
8CMJMNLCMN6DK2M(97N?EIJDNGFNGHFLIEEM@N5M<KJMNJMDK-GH:NGLN<JKDNLCM
DKBHLGH:N5JIA2ML;N&IGEBJMNLKNLBJHNK<<NLCMN>K8MJN<GJFLNDI=NJMFBELNGH
FMJGKBFNMEMALJGAIENFCKA2+NGHBJ=NKJN@MILC;
?E8I=FN@GFACIJ:MNLCMN5JIHACNAGJABGLN5M<KJM
FMJ-GAGH:NIHN?9NKJN?9(,9N6DK2M(97N?EIJD;N&GJFL+NLBJHNK<<NLCMN?9
>K8MJNILNLCMNAGJABGLN5JMI2MJNKJN<BFMN5K ;N*M L+NJMDK-MNLCMN5ILLMJ=
<JKDN6DK2M(97N?EIJDFN8GLCN5ILLMJ=N5I
A2!B>;N&GHIEE=+N>JMFFNIH@
CKE@NLCMNLMFLN5BLLKH;
1.
Insert a flathead screwdriver between the mounting bracket pin and
the mounting bracket.
2. Pry the Smoke/CO Alarm away from the bracket by turning both
the screwdriver and the Smoke/CO Alarm counterclockwise (left)
at the same time.
37N%1)$?*1*30N)1$71
3'1N#)?913N079
Insert the flathead screwdriver
between the locking pin and the
lock, and pry the pin ou
t of the lock.
37N*079N3'1N#?331)N97$%?)3$1*3/
Once the Smoke/CO Alarm is installed, you must disconnect it from the AC
power before unlocking the battery compartment.
10193).9?0N6'79N'??),;N3BJHNK<<NLCM
>K8MJNLKNLCMNIJMIN8CMJMN
LCMN6DK2M(97N?EIJDNGFNGHFLIEEM@N5M<KJMNJMDK-GH:NGLN<JKDNLCMNDKBHLGH:
5JIA2ML;N&IGEBJMNLKNLBJHNK<<NLCMN>K8MJN<GJFLNDI=NJMFBELNGHNFMJGKBFNMEMALJGAIE
FCKA2+NGHBJ=NKJN@MILC;
1. Remove the Smoke/CO Alarm from the mounting bracket. If the unit is
locked to the bracket, see the section “To Deactivate the Locking
Feature.”
2. Disconnect the power connector by gently prying it away
from the back of the Smoke/CO Alarm.
3. Insert a flathead screwdriver under the head of the
locking pin, and gently pry it out of the battery
compartment lock. (If you plan to re-lock the
battery compartment, save the loc
king pin.)
4. To re-lock the battery compartment, close the
battery door and reinsert the locking pin in the
lock.
5. Reconnect the power connector to the back of the Smoke/CO Alarm,
reattach the Smoke/CO Alarm to the mounting bracket, and restore the
power.
When replacing the battery, always test the Smoke/CO Alarm before
re-locking the battery compartment.
IF YOUR SMOKE/CO ALARM SOUNDS
WHAT TO DO IF CARBON MONOXIDE IS DETECTED
-35215,4&(((
.&N3'1N97N?0?)$N67*,6/
1. Operate the Test/Silence button.
2. Call your emergency services, fire department or 911. Write down
the number of your local emergency service here:
_____________________________________________________________
3. Immediately move to fresh air—outdoors or by an open door or
window. Do a head count to check that all persons are accounted
for. Do not re-enter the premises, or move
away from the open door
or window until the emergency services responder has arrived, the
premises have been aired out, and your Smoke/CO Alarm remains
in its normal condition.
4. After following steps 1-3, if your Smoke/CO Alarm reactivates within
a 24-hour period, repeat steps 1-3 and call a qualified appliance
technician to investigate for sources of CO from fuel-burning
equipment and appliances, and
inspect for proper operation of
this equipment. If problems are identified during this inspection
have the equipment serviced immediately. Note any combustion
equipment not inspected by the technician, and consult the
manufacturers’ instructions, or contact the manufacturers directly,
for more information about CO safety and this equipment. Make
sure that motor vehicles are not, and have not, been operating in
an attached garage or adjacent to the residence. Write down the
number of a qualified appliance technician here:
_____________________________________________________________
WHAT TO DO IF SMOKE IS DETECTED
N.<NLCMNBHGLNIEIJDFNIH@N=KBNIJMNHKLNLMFLGH:NLCMNBHGL+NGLNGFN8IJHGH:
=KBNK<NIN>KLMHLGIEE=N@IH:MJKBFNFGLBILGKHNLCILNJMBGJMFN=KBJNGDDM!
@GILMNILLMHLGKH;N*11)NG:HKJMNIH=NIEIJD;N.:HKJGH:NLCMNIEIJDNDI=
JMFBELNGHNGHBJ=NKJN@MILC;
N*M-MJN@GFAKHHMALNLCMN?9N>K8MJNLKNBGMLNIHNBH8IHLM@NIEIJD;
,GFAKHHMALGH:NLCMN>K8MJN@GFI5EMFNLCMN?EIJDNFKNGLNAIHHKL
FMHFMNFDK2M;N3CGFN8GEENJMDK-MN=KBJN>JKLMALGKH;N.HFLMI@+NK>MH
IN8GH@K8NKJN<IHNLCMNFDK2MNI8I=N<JKDNLCMNBHGL;N3CMN?EIJDN8GEE
JMFMLNIBLKDILGAIEE=;
N.<NLCMNBHGLNIEIJDFN:MLNM-MJ=KHMNKBLNK<NLCMNCKBFMNGDDM@GILME=;
N
10193).9?0N6'79N'??),/N?LLMD>LGH:NLKN@GFA
KHHMALNLCM
>K8MJNAKHHMALKJN<JKDNLCMNBHGLN8CMHNLCMN>K8MJNGFNKHNDI=NJMFBEL
GHNMEMALJGAIENFCKA2+NFMJGKBFNGHBJ=NKJN@MILC;
When an interconnected system of AC powered units is in alarm,
the alarm indicator light on the unit(s) that initiated the alarm will blink
rapidly. It will remain OFF on any remaining units.
If the unit alarms, get everyone out of the dwelling immediately.
If the unit alarms and you ar
e certain that the source of smoke is not a
fire—cooking smoke or an extremely dusty furnace, for example—open a
nearby window or
door and fan the smoke away from the unit. Use the
Silence Feature to silence the Alarm. This will silence the alarm, and
once the smoke clears the unit will reset itself automatically.
WHAT TO DO IN CASE OF FIRE
Don’t panic; stay calm. Follow your family escape plan.
Get out of the house as quickly as possible. Don’t stop to get
dressed or collect anything.
Feel doors with the back of your hand before opening them.
If a door is cool, open it slowly. Don’t open a hot door. Keep doors
and windows closed, unless you must escape through them.
Cover your nose and mouth with a cloth (preferably damp).
Take short, shallow breaths.
Meet at your planned meeting place outside your home,
and do a head count to make sure everybody got out safely.
Call the Fire Department as soon as possible from outside.
Give your address, then your name.
Never go back inside a burning building for any reason.
Contact your Fire Department for ideas on making your home safer.
?EIJDFNCI-MN-IJGKBFNEGDGLILGKHF;N6MMNMHMJIEN0GDGLILGKHFNK<
6DK2M(97N?EIJDFN<KJN@MLIGEF;
“SMART INTERCONNECT” FEATURE
This Alarm includes "Smart Interconnect" which enables the Alarm to be
interconnected with other BRK Smoke, Heat, and "Smart Interconnect"
CO Alarms. When smoke is detected, all Alarms will sound the smoke
horn pattern. When CO is detected, "Smart Interconnect" Alarms will
sound the CO horn pattern. Alarms that do not have the "Smart
Interconnect" Feature will remain silent during a CO alarm.
.<N=KBNCMIJNLCMNIEIJDNCKJHNFKBH@NN5MM>F+N>IBFM+NN5MM>F+
>IBFMNIH@NLCMN)1,N6$71NEG:CLNGFN<EIFCGH:+NFDK2MNCIF
5MMHN@MLMALM@;N1-IABILMNM-MJ=KHMN<JKDNLCMN5BGE@GH:;
)15$6246/2135+*63'15$64+2,.4)6-35215,4&
!#6#/6/6"6-!/6%//"6"06#-#6-35215,4&
?ALBILGKHNK<N=KBJN97N?EIJDNGH@GAILMFNLCMN>JMFMHAMNK<NAIJ5KH
DKHK G@MN97N8CGACNAIHN2GEEN=KB;N.HNKLCMJN8KJ@F+N8CMHN=KBJN97
?EIJDNFKBH@F+N=KBNDBFLNHKLNG:HKJMNGL
9KHHMALNLCGFNBHGLN7*0NLKNKLCMJNAKD>ILG5EMNBHGLF;N6MMN'K8
3KN.HFLIEEN3CGFN6DK2M(97N?EIJDN<KJN@MLIGEF;N,KNHKLNAKHHMALN
GLNLKNIH=NKLCMJNL=>MNK<NIEIJDNKJNIB GEGIJ=N@M-GAM;N9KHHMALGH:
IH=LCGH:NMEFMNLKNLCGFNBHGLNDI=N@IDI:MNGLNKJN>JM-MHLNGLN<JKD
K>MJILGH:N>JK>MJE=;
3CMN5ILLMJ=NAKD>IJLDMHLNJMFGFLFNAEKFGH:NBHEMFFNIN5ILLMJ=NGF
GHFLIEEM@;N3CGFN8IJHFN=KBNLCMNBHGLN8GEENHKLNK>MJILMNBH@MJN,9
>K8MJN8GLCKBLNIN5ILLMJ=;
,KNHKLNFLIH@NLKKNAEKFMNLKNLCMNBHGLN8CMHNLCMNIEIJDNGFNFKBH@GH:;
.LNGFNEKB@NLKN8I2MN=KBNGHNIHNMDMJ:MHA=;N1 >KFBJMNLKNLCMNCKJH
ILNAEKFMNJIH:MNDI=NCIJDN=KBJNCMIJGH:;N
,KNHKLN>IGHLNK-MJNLCMNBHGL;N%IGHLNDI=NAEK:NLCMNK>MHGH:FNLKNLCM
FMHFGH:NACID5MJFNIH@N>JM-MHLNLCMNBHGLN<JKDNK>MJILGH:N>JK>MJE=;
USERS MANUAL
Smoke & Carbon
Monoxide Alarm
?9N%K8MJM@N6DK2MN
9IJ5KHN$KHK G@MN?EIJDN
8GLCN#ILLMJ=N#IA2!B>+
6GEMHAMN&MILBJMNIH@N
0ILACGH:N?EIJD
Model SC9120B
Input: 120V AC ~
60 Hz, 0.09A
.$%7)3?*3N%01?61N)1?,N9?)1&00N?*,N6?1
This user’s manual contains important information about your Alarm’s
operation. If you are installing the Alarm for use by others, you must
leave this manual — or a copy of it with the end user.
Model
SC9120B
Printed in Mexico
M08-0094-030 "NNN04/14
Both locking features use locking pins, molded into the mounting bracket. Using needle nose pliers or a utility knife, remove one or both pins, depending on
which locking features you use.
?0?)$!$71N37N&)16'N?.)
.<N=KBNCMIJNLCMNIEIJDNCKJHNFKBH@NN5MM>F+N>IBFM+N
N5MM>F+N>IBFM+NIH@NLCMN)1,N97NEG:CLNGFN<EIFCGH:+N
DK-MNM-MJ=KHMNLKNINFKBJAMNK<N<JMFCNIGJ;
0.631,N37
0N"NIH@
0N
63?*,?),6
'?3N7N.00N611N?*,N'1?)N.3'N3'.6N?0?)$
H@MJN*KJDIEN7>MJILGKHF
'KJH/ Silent
%K8MJ(6DK2MN01,/ Constant Green
97N01,/ Off
CMHNKBN3MFLNLCMN?EIJD
'KJH/ 3 beeps, pause, 3 beeps
%K8MJ(6DK2MN01,/ AC Power (LED Green); Battery Power (LED off)
97N01,/ Off, followed by
'KJH/ 4 beeps, pause, 4 beeps
%K8MJ(6DK2MN01,/ Turns back On
97N01,/ Flashes Red in sync with the horn pattern
.<N#ILLMJ=N#MAKDMFN0K8NKJNGFN$GFFGH:
'KJH/ chi
rps once a minute
%K8MJ(N6DK2MN01,/ Flashes Green once a minute until reset. Low
Battery latch is now engaged. (See Latching Features note
below.) Green LED On for 2 seconds/Off for two seconds.
97N01,/ Off
.<N?EIJDNGFN*KLN7>MJILGH:N%JK>MJE=N$?0&*93.7*N6.*?0
'KJH/ 3 chirps every minute
%K8MJ(6DK2MN01,/ Green LED 3 Flashes approx. once a minute
97N01,/ Off
?EIJDNCIFNJMIACM@NGLFN1H@NK<N0G<M
'KJH/ 5 chirps every
minute
%K8MJ(6DK2MN01,/ Green LED 5 Flashes approx. once a minute
97N01,/ Off
?EIJDN0M-MEFNK<N97NIJMN,MLMALM@
'KJH/ 4 beeps, pause, 4 beeps
%K8MJ(6DK2MN01,/ On
97N01,/ During Alarm: Flashes Red in sync with the horn pattern.
After Alarm: Flashes Red On for 2 seconds/Off for 2 seconds.
CO Alarm Latch is now engaged. (See LATCHING FEATURES
section for details).
6DK2MNGFN,MLMALM@
'KJH/ 3 beeps, pause, 3 beeps
%K8MJ(6
DK2MN01,/ During Alarm: Flashes Red in sync with the
horn pattern. After Alarm: Flashes Red On for 2 seconds/Off
for 2 seconds. Smoke Alarm Latch is now engaged. (See
LATCHING FEATURES section for details).
97N01,/ Off
6DK2MN?EIJDNGFN6GEMHAM@
'KJH/ Off
%K8MJ(6DK2MN01,/ Flashes Red
97N01,/ Off
97N?EIJDNGFN6GEMHAM@
'KJH/ Off
%K8MJ(6DK2MN01,/ AC Power (LED Green); Battery Power (LED off)
97N01,/ Flashes Red
0ILACGH:N&MILBJMFN*KLM/NGLCKBLN?9N%K8MJNIH@NJBHHGH:NKHN5ILLMJ=
KHE=+N0K8N#ILLMJ=N0ILACNKJN?EIJDN0ILACNIJMNKHE=NMH:I:M@N<KJNI5KBL
"NDGHBLMFNLKNAKHFMJ-MN>K8MJ;N0K8N#ILLMJ=N0ILACNIH@N?EIJDN0ILAC
@KNHKLNK>MJILMN8GLCNINDGFFGH:N5ILLMJ=NIH@NHKN?9N%K8MJ;
USING THE SILENCE FEATURES
*M-MJNJMDK-MNLCMN5ILLMJGMFNLKNBGMLNIHNBH8IHLM@NIEIJD;N)MDK-GH:
LCMN5ILLMJGMFN@GFI5EMFNLCMNIEIJDNIH@NJMDK-MFN=KBJN>JKLMALGKH;
The Silence Feature is intended to temporarily silence the horn while
you identify and correct the problem. Do not use the Silence Feature in
emergency situations. It will not correct a CO problem or extinguish a
fire.
The Silence Feature can temporarily
quiet an unwanted alarm for several
minutes. You can silence this Smoke/CO Alarm by pressing the Test/
Silence button on the alarm cover until you hear an acknowledge chirp.
After the Test/Silence button is released, the Red LED blinks during the
silence mode.
SILENCING THE LOW BATTERY WARNING
This Silence Feature can temporarily quiet the low battery warning
“chirp” for up to 8 hours if AC power is present. Press the Test/Silence
button on the Alarm cover until you hear the acknowledge “chirp”.
Once the low battery warning “chirp” silence feature is activated, the
unit continues to flash the green light once a minute for 8 hours. After
8 hours, the low battery “chirp” will resume. The Alarm will continue to
operate as long as AC power is supplied. Note, if battery is missing or
dead, Low Battery Si
lence cannot be activated and alarm with continue
to chirp approximately once per minute. However, JM>EIAMNLCMN5ILLMJGMF
IFNFKKHNIFN>KFFG5EM+ to maintain protection in event of a power outage.
3KN@MIALG-ILMNLCGFN<MILBJM/NPress the Test/Silence button again.
The unit will go into Test Mode and the low battery warning will resume
(LED flashes and unit sounds “chirp” once a minute).
3KNFGEMHAMN?EIJDFNGHNIHNGHLMJAKHHMALM@NFMJGMF/
To silence an interconnected series of Smoke/CO Alarms, you must
press the Test/Silence button on the initiating alarm (The unit with the
flashing red light; the red light will be off on all other Alarms.). If you
press the Test/Silence on any other Alarm, it will only silence that unit,
not the whole interconnected series.
CMHNLCMN6DK2MN?EIJDNGF
6GEMHAM@
CMHNLCMN97N?EIJDNGFN
6GEMHAM@
The Smoke Alarm will remain
silent for up to 15 minutes, then
return to normal operation.
If the smoke has not cleared–or
continues to increase–the device
will go back into alarm.
The CO alarm will remain silent
for up to 4 minutes.
After 4 minutes, if CO levels
remain potentially dangerous the
horn will start sounding again.
SILENCING THE END OF LIFE SIGNAL
This silence feature can temporarily quiet the End of Life warning “chirp”
for up to 2 days. You can silence the End of Life warning “chirp” by
pressing the Test/Silence button. The horn will chirp, acknowledging
that the End of Life silence feature has been activated.
After approximately 2 days, the End of Life “chirp” will resume. After
approximately 2-3 weeks the End of Life warning cannot be silenced.
Printed in Mexico
M08-0094-157176 K1 03/17
2017
SUGGESTED AREAS FOR INSTALLING 
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
SMOKE ALARM WITH 
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION 
SMOKE/CO ALARMS
SMOKE ALARMS
KEY:
Suggested locations are based on
NFPA recommendations (NFPA 72 
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always 
refer to national and local codes 
before beginning any installation.
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
6
7
8
4
3
1
5
4
3
1
5
2
A
B
}
}
1
2
3
5
6
4
2
3
9
7
8
Mounting Bracket Lock
Battery Drawer Lock
Locking Pin
© 2017 BRK Brands, Inc. All rights reserved. Distributed by BRK Brands,
Inc.
BRK Brands, Inc. is a subsidiary of Newell Brands Inc. (NYSE:NWL)
First Alert
®
is registered trademark of The First Alert Trust
3901 Liberty
Street Road, Aurora, IL 60504-8122
Consumer Affairs: (800) 323-9005
www.rstalert.com
www.brkelectronics.com

Summary of content (2 pages)