Installation Guide

1 2 3 4 5 6
LOCATIONS TO AVOID FOR SMOKE ALARMS
For best performance, it is recommended you AVOID installing Smoke Alarms in these areas:
Where combustion particles are produced. Combustion particles form when something burns.
Areas to avoid include poorly ventilated kitchens, garages, and furnace rooms. Keep units at
least 20 feet (6 meters) from the sources of combustion particles (stove, furnace, water heater,
space heater) if possible. In areas where a 20-foot (6-meter) distance is not possible – in
modular, mobile, or smaller homes, for example – it is recommended the Smoke Alarm be
placed as far from these fuel-burning sources as possible. The placement recommendations
are intended to keep these Alarms at a reasonable distance from a fuel-burning source,
and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is
placed directly next to a fuel-burning source. Ventilate these areas as much as possible.
In air streams near kitchens. Air currents can draw cooking smoke into
the sensing chamber of a Smoke Alarm near the kitchen.
In very damp, humid or steamy areas, or directly near bathrooms with showers. Keep
units at least 10 feet (3 meters) away from showers, saunas, dishwashers, etc.
Where the temperatures are regularly below 40˚ F (4.4˚ C) or above 100˚ F (37.8˚ C), including
unheated buildings, outdoor rooms, porches, or unfinished attics or basements.
In very dusty, dirty, or greasy areas. Do not install a Smoke Alarm directly over
the stove or range. Keep laundry room Smoke Alarms free of dust or lint.
Near fresh air vents, ceiling fans, or in very drafty areas. Drafts can blow smoke
away from the unit, preventing it from reaching the sensing chamber.
In insect infested areas. Insects can clog openings to the
sensing chamber and cause unwanted alarms.
Less than 12 inches (305mm) away from fluorescent lights.
Electrical “noise” can interfere with the sensor.
In “dead air” spaces. “Dead air” spaces may prevent smoke from reaching the Smoke Alarm.
Avoiding Dead Air Spaces
“Dead air” spaces may prevent smoke from reaching the Smoke Alarm. To
avoid dead air spaces, follow the installation recommendations below.
On ceilings, install Smoke Alarms as close to the center of the ceiling as possible. If this is
not possible, install the Smoke Alarm at least 4 inches (102 mm) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke Alarms should be placed
between 4 and 12 inches (102 and 305 mm) from the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling, install the first Smoke Alarm within 3
feet (0.9 meters) of the peak of the ceiling, measured horizontally. Additional Smoke
Alarms may be required depending on the length, angle, etc. of the ceiling’s slope.
Refer to NFPA 72 for details on requirements for sloped or peaked ceilings.
ABOUT SMOKE ALARMS
Battery (DC) operated Smoke Alarms: Provide protection even when
electricity fails, provided the batteries are fresh and correctly installed. Units
are easy to install, and do not require professional installation.
AC powered Smoke Alarms: Can be interconnected so if one unit senses smoke,
all units alarm. They do not operate if electricity fails. AC with battery (DC) back-
up: will operate if electricity fails, provided the batteries are fresh and correctly
installed. AC and AC/DC units must be installed by a qualified electrician.
WIRELESS INTERCONNECT Smoke Alarms with battery (DC) back-up: Interconnects with all
WIRELESS INTERCONNECT enabled Smoke and Smoke/CO Alarms without wires or connectors,
so when one alarm sounds, they all sound. Will operate if electricity fails, provided the batteries are
fresh and correctly installed. Units are easy to install, and do not require professional installation.
Smoke Alarms for Solar or Wind Energy users and battery backup power systems:
AC powered Smoke Alarms should only be operated with true or pure sine wave inverters.
Operating this Smoke Alarm with most battery- powered UPS (uninterruptible power supply)
products or square wave or “quasi sine wave” inverters will damage the Alarm. If you are
not sure about your inverter or UPS type, please consult with the manufacturer to verify.
Smoke Alarms for the hearing impaired: Special purpose Smoke Alarms should
be installed for the hearing impaired. They include a visual alarm and an audible
alarm horn, and meet the requirements of the Americans With Disabilities Act.
Can be interconnected so if one unit senses smoke, all units alarm.
Smoke alarms are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.
All these Smoke Alarms are designed to provide early warning of fires if located, installed and
cared for as described in the user’s manual, and if smoke reaches them. If you are unsure which
type of Smoke Alarm to install, refer to Chapter 2 of the National Fire Protection Association (NFPA)
Standard 72 (National Fire Alarm and Signaling Code) and NFPA 101 (Life Safety Code). National
Fire Protection Association, One Batterymarch Park, Quincy, MA 02269-9101. Local building
codes may also require specific units in new construction or in different areas of the home.
SPECIAL COMPLIANCE CONSIDERATIONS
This Smoke Alarm is suitable for use in apartments, condominiums, townhouses, hospitals, day
care facilities, health care facilities, boarding houses, group homes and dormitories provided
a primary fire detection system already exists to meet fire detection requirements in common
areas like lobbies, hallways, or porches. Using this Smoke Alarm in common areas may not
provide sufficient warning to all residents or meet local fire protection ordinances/regulations.
This Smoke Alarm alone is not a suitable substitute for complete fire detection systems
in places housing many people—like apartment buildings, condominiums, hotels, motels,
dormitories, hospitals, health care facilities, nursing homes, day care facilities, or group homes
of any kind. It is not a suitable substitute for complete fire detection systems in warehouses,
industrial facilities, commercial buildings, and special-purpose non-residential buildings which
require special fire detection and alarm systems. Depending on the building codes in your
area, this Smoke Alarm may be used to provide additional protection in these facilities.
In new construction, most building codes require the use of AC or AC/DC powered Smoke
Alarms only. In existing construction, AC, AC/DC, or DC powered Smoke Alarms can be used
as specified by local building codes. Refer to NFPA 72 (National Fire Alarm and Signaling
Code) and NFPA 101 (Life Safety Code), local building codes, or consult your Fire Department
for detailed fire protection requirements in buildings not defined as “households”.
HUD MAP Program
Certain HUD battery powered Smoke Alarm applications, especially those that fall under
HUD 223(f) MAP (Multi-family Accelerated Processing), may require a 10 Year sealed tamper
resistant battery. This alarm does not meet that requirement. Substitute First Alert SA340B.
FCC Compliance
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance
with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that the interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that of the receiver.
Consult the dealer or an experienced radio or TV technician for help.
Changes or modifications to the product, not expressly approved by First Alert /
BRK Brands, Inc., could void the user’s authority to operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation. FCC ID: M7U5001L
LIMITATIONS OF SMOKE ALARMS
Smoke Alarms have played a key role in reducing deaths resulting from home fires worldwide.
However, like any warning device, Smoke Alarms can only work if they are properly located,
installed, and maintained, and if smoke reaches them. They are not foolproof.
Smoke alarms may not waken all individuals. Practice the escape plan at least twice a year,
making sure that everyone is involved – from kids to grandparents. Allow children to master fire
escape planning and practice before holding a fire drill at night when they are sleeping. If children
or others do not readily waken to the sound of the smoke alarm, or if there are infants or family
members with mobility limitations, make sure that someone is assigned to assist them in fire
drill and in the event of an emergency. It is recommended that you hold a fire drill while family
members are sleeping in order to determine their response to the sound of the smoke alarm while
sleeping and to determine whether they may need assistance in the event of an emergency.
Smoke Alarms cannot work without power. Battery operated units cannot work if the batteries
are missing, disconnected or dead, if the wrong type of batteries are used, or if the batteries are not
installed correctly. AC units cannot work if the AC power is cut off for any reason (open fuse or circuit
breaker, failure along a power line or at a power station, electrical fire that burns the electrical wires,
etc.). If you are concerned about the limitations of battery or AC power, install both types of units.
Smoke Alarms cannot detect fires if the smoke does not reach them. Smoke from fires in
chimneys or walls, on roofs, or on the other side of closed doors may not reach the sensing chamber
and set off the alarm. That is why one unit should be installed inside each bedroom or sleeping area—
especially if bedroom or sleeping area doors are closed at night—and in the hallway between them.
Smoke Alarms may not detect fire on another floor or area of the home. For example, a stand-
alone unit on the second floor may not detect smoke from a basement fire until the fire spreads.
This may not give you enough time to escape safely. That is why recommended minimum protection
is at least one unit in every sleeping area, and every bedroom on every level of your home. Even
with a unit on every floor, stand-alone units may not provide as much protection as interconnected
units, especially if the fire starts in a remote area. Some safety experts recommend installing
interconnected AC powered units with battery back-up (see “About Smoke Alarms”) or professional
fire detection systems, so if one unit senses smoke, all units alarm. Interconnected units may
provide earlier warning than stand-alone units since all units alarm when one detects smoke.
Smoke Alarms may not be heard. Though the alarm horn in this unit meets or exceeds
current standards, it may not be heard if: 1) the unit is located outside a closed or
partially closed door, 2) residents recently consumed alcohol or drugs, 3) the alarm is
drowned out by noise from stereo, TV, traffic, air conditioner or other appliances, 4)
residents are hearing impaired or sound sleepers. Special purpose units, like those with
visual and audible alarms, should be installed for hearing impaired residents.
Smoke Alarms may not have time to alarm before the fire itself causes damage,
injury, or death, since smoke from some fires may not reach the unit immediately.
Examples of this include persons smoking in bed, children playing with matches,
or fires caused by violent explosions resulting from escaping gas.
Smoke Alarms are not foolproof. Like any electronic device, Smoke Alarms are
made of components that can wear out or fail at any time. You must test the unit
weekly to ensure your continued protection. Smoke Alarms cannot prevent or
extinguish fires. They are not a substitute for property or life insurance.
Smoke Alarms have a limited life. The unit should be replaced immediately if it is not
operating properly. You should always replace a Smoke Alarm after 10 years from date
of purchase. Write the purchase date on the space provided on back of unit.
LIMITED WARRANTY
BRK Brands, Inc., (“BRK”) the maker of First Alert
®
brand products warrants that for a period of ten years from the date of purchase, this product will be free from defects in material and
workmanship. BRK, at its option, will repair or replace this product or any component of the product found to be defective during the warranty period. Replacement will be made with a new or
re- manufactured product or component. If the product is no longer available, replacement may be made with a similar product of equal or greater value. This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. Proof of purchase is required to obtain warranty
performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to alter, modify or any way change the terms and conditions of this warranty.
This warranty does not cover normal wear of parts or damage resulting from any of the following: negligent use or misuse of the product, use on improper
voltage or current, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center. Further,
the warranty does not cover Acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.
BRK shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty. Except to the extent prohibited by applicable law,
any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above warranty. Some states, provinces or jurisdictions
do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the above limitations or exclusion
may not apply to you. This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or province to province.
How to Obtain Warranty Service
Service: If service is required, do not return the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division
at 1-800-323-9005. To assist us in serving you, please have the model number and date of purchase available when calling.
For Warranty Service return to: BRK Brands, Inc., 1301 Joe Battle, El Paso, TX 79936
Battery: BRK Brands, Inc. make no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose with respect to battery.
Visit www.firstalert.com for more information.
Printed in Mexico M08-0194-007 K1 5/16
USER’S MANUAL
WIRELESS
INTERCONNECT
BATTERY OPERATED
SMOKE ALARM
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Smoke
Alarm’s operation. If you are installing this Smoke Alarm for use by others,
you must leave this manual—or a copy of it—with the end user.
WIRELESS INTERCONNECT Enabled
Voice with Programmable Location
Two Latching Features
Optipath 360 Technology
Two Silence Features
Printed in Mexico
M08-0194-007 K1 5/16
CONFORMS TO
UL STD 217
Model SA511
© 2016 BRK Brands, Inc. All rights reserved. Distributed by BRK Brands, Inc. First Alert
®
is registered
trademark of The First Alert Trust. 3901 Liberty Street Road, Aurora, IL 60504-8122 Consumer Affairs:
(800) 323-9005 www.firstalert.com www.brkelectronics.com
All First Alert
®
and BRK
®
Smoke Alarms conform to regulatory requirements,
including UL217 and are designed to detect particles of combustion.
Smoke particles of varying number and size are produced in all fires.
Ionization technology is generally more sensitive than photoelectric technology at
detecting small particles, which tend to be produced in greater amounts by flaming
fires, which consume combustible materials rapidly and spread quickly. Sources of
these fires may include paper burning in a wastebasket, or a grease fire in the kitchen.
Photoelectric technology is generally more sensitive than ionization technology
at detecting large particles, which tend to be produced in greater amounts
by smoldering fires, which may smolder for hours before bursting into flame.
Sources of these fires may include cigarettes burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on
each level and in every bedroom of your home.
INTRODUCTION
Thank you for choosing First Alert
®
for your Smoke Alarm needs. You have purchased a state-of-
the-art Smoke Alarm designed to provide you with early warning of a fire. Key features include:
WIRELESS INTERCONNECT Enabled. Alarm automatically communicates
with other WIRELESS INTERCONNECT enabled alarms when installed.
Exclusive Voice Warning with Location. Will tell you the preprogrammed location of the
initiating unit and danger detected. Programmable up to 11 locations (ex. “basement).
When alarms sounds, if programmed for basement it will say “Warning, evacuate, smoke
in basement” along with all other installed WIRELESS INTERCONNECT Voice alarms.
Spread Spectrum Horn Tone. Lower and varying horn frequency makes it easier for elderly
with normal age related hearing loss to hear horn. Sweeps through the 2200 – 3400 Hz range.
RF Interconnect. Reliable and secure radio frequency communication between alarms.
915MHz frequency with 65,000 security codes and 3 channel frequency hopping.
Optipath 360 Technology
. Provides 360 degrees of direct access to the smoke sensor.
Single Button Test/Silence. Eliminates confusion. Depending on what mode the alarm
is in, pushing the button provides different functions such as testing the alarm, silencing
the alarm, re-testing the alarm when in silence and clearing the Latching features.
Two Silence Features. Temporarily silence low battery chirp for up to eight hours
before replacing low battery or silence an unwanted alarm for several minutes.
Two Latching Features. Alarm Latch: Easily identifies initiating alarm even after alarm
condition has subsided. Low Battery Latch: Identifies which unit is in low battery condition.
Perfect Mount System. Includes a gasketless base for easy installation and a mounting bracket
that keeps the alarm secure over a wide rotation range to allow for perfect alignment.
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking materials properly. Never
smoke in bed. 2) Keep matches or lighters away from children; 3) Store flammable materials in
proper containers; 4) Keep electrical appliances in good condition and don’t overload electrical
circuits; 5) Keep stoves, barbecue grills, fireplaces and chimneys grease- and debris-free; 6)
Never leave anything cooking on the stove unattended; 7) Keep portable heaters and open
flames, like candles, away from flammable materials; 8) Don’t let rubbish accumulate.
Keep alarms clean, and test them weekly. Replace alarms immediately if they are not working
properly. Smoke Alarms that do not work cannot alert you to a fire. Keep at least one working
fire extinguisher on every floor, and an additional one in the kitchen. Have fire escape ladders
or other reliable means of escape from an upper floor in case stairs are blocked.
BEFORE YOU INSTALL THIS SMOKE ALARM
Important! Read “Recommended Locations for Smoke Alarms” and “Locations to Avoid
for Smoke Alarms” before beginning. This unit monitors the air, and when smoke reaches
its sensing chamber, it alarms. It can give you more time to escape before fire spreads.
This unit can ONLY give an early warning of developing fires if it is installed, maintained and
located where smoke can reach it, and where all residents can hear it, as described in this
manual. This unit will not sense gas, heat, or flame. It cannot prevent or extinguish fires.
Understand The Different Type of Smoke Alarms
Battery powered or electrical? Different Smoke Alarms provide different
types of protection. See “About Smoke Alarms” for details.
Know Where To Install Your Smoke Alarms
Fire Safety Professionals recommend at least one Smoke Alarm on every level of your home, in
every bedroom, and in every bedroom hallway or separate sleeping area. See “Recommended
Locations For Smoke Alarms” and “Locations To Avoid For Smoke Alarms” for details.
Know What Smoke Alarms Can and Can’t Do
A Smoke Alarm can help alert you to fire, giving you precious time to escape. It can only sound
an alarm once smoke reaches the sensor. See “Limitations of Smoke Alarms” for details.
Check Your Local Building Codes
This Smoke Alarm is designed to be used in a typical single-family home. It
alone will not meet requirements for boarding houses, apartment buildings,
hotels or motels. See “Special Compliance Considerations” for details.
This unit will not alert hearing impaired residents. It is recommended
that you install special units which use devices like flashing
strobe lights to alert hearing impaired residents.
Unit will not operate without battery power. The Smoke Alarm cannot work until
you install the batteries in the correct position (Match “+” to “+” and “-” to “-”).
This Smoke Alarm has a battery drawer which resists
closing unless batteries are installed.
Do not install this unit over an electrical junction box. Air currents around junction
boxes can prevent smoke from reaching the sensing chamber and prevent the unit
from alarming. Only AC powered units are intended for installation over junction boxes.
Do not stand too close to the unit when the alarm is sounding. It is loud to wake you
in an emergency. Exposure to the horn at close range may harm your hearing.
Do not paint over the unit. Paint may clog the openings to the sensing
chamber and prevent the unit from operating properly.
STEP BY STEP GUIDE TO PROGRAMMING THIS ALARM
FOR FIRST TIME AND WHEN CHANGING BATTERIES
Action: Alarm Will Say:
1. Insert batteries (2, AA batteries).
“Welcome, First Alert Smoke Alarm.”
“No location programmed” if first time or
“[Location, example: “Basement”] location
programmed” when changing batteries.
“To select location, press and
hold test button now.”
2. Press & Hold Test Button if you would
like to program the location or change
the location of the Alarm. Release
button after Alarm responds.
“To save location, press and hold test
button after location is heard.” Alarm will
speak list of locations (see below).
3. After you hear the location of
where you are placing the Alarm,
Press & Hold the Test Button.
“[Location, example: “Basement”]
location saved.
If no location is chosen: “No location saved.”
Your Alarm has now been programmed for the location of your choice. Available locations:
Basement Kitchen Child’s Bedroom
Living Room Dining Room Master Bedroom
Family Room No Location Guest Bedroom
Office Hallway Utility Room
ADDING AND LINKING ADDITIONAL
WIRELESS INTERCONNECT ALARMS
NOTE: Steps 1 through 3 below need to be completed within two minutes. If
more than two minutes pass, the Green power LED will stop blinking. Simply open
the battery drawer of the second Alarm and repeat steps 1 through 3.
1. Press and hold the test button and
then close the battery drawer.
2. Once you hear the unit chirp, release the
test button. The Green power LED will
start to blink indicating the WIRELESS
INTERCONNECT Alarm is waiting for
program data from one of the other setup
WIRELESS INTERCONNECT Alarms.
3. Press and hold the test button on the
first Alarm, until the second Alarm
chirps and its Green power LED stops
blinking. Then release the test button.
4. Press and hold the test button on the first Alarm, until the second Alarm chirps
and its Green power LED stops blinking. Then release the test button.
5. If you purchased a Talking Smoke Alarm, you will now be prompted to set
the Alarm’s location. Follow the directions given by the Alarm.
6. If you have purchased the hardwired battery back-up WIRELESS
INTERCONNECT Alarm, you can now connect the hardwired Alarm by
installing the three-wire connector on the ceiling to the Alarm.
7. Repeat steps 1-6 for additional WIRELESS INTERCONNECT Alarms.
You have now successfully linked your new WIRELESS INTERCONNECT
Alarms. To add additional Alarms at a later time, follow steps 1 through 6.
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM
Under Normal Operations
Voice: Silent
Horn: Silent
Power LED: Flashes Green once/minute
When You Test the Alarm
Voice:Testing.” Horn: 3 beeps, pause, 3 beeps; Voice: “Warning,
evacuate smoke in [Location, example: “Basement”]. Evacuate.
Smoke LED: Flashes Red in sync with the horn pattern
If Battery Becomes Low
Voice: “Replace battery in [Location, example “Basement”].” Repeated every 5 hours
Horn: chirps once a minute
Power LED: Flashes Green On for 2 seconds/Off for 2
seconds. Low Battery Latch is now engaged.
If Alarm is Not Operating Properly (MALFUNCTION SIGNAL)
Voice: “Detector error in [Location, example “Basement”],
please see manual.” Repeated every 5 hours
Horn: Three rapid chirps every minute
Smoke LED: Flashes approximately once a minute
Smoke is Detected
Horn: 3 beeps, pause, repeating 3 times
Voice: “Warning, evacuate smoke in [Location, example: “Basement”]. Evacuate.
Smoke LED: During Alarm: Flashes Red in sync with the horn pattern. After Alarm:
Flashes Red On for 2 seconds/Off for 2 seconds. Smoke Alarm Latch is now engaged.
Smoke Alarm is Silenced
Horn: Off
Smoke LED: Flashes Red
WIRELESS OPERATION
First Alert
®
WIRELESS INTERCONNECT Technology is the easy, cost-effective way to provide
your family with whole-home safety. All WIRELESS INTERCONNECT Alarms communicate with
each other without wires or connectors. When one Alarm sounds, they all sound. This provides
your family with an earlier warning of potential danger, and gives you more time to react.
The communication distance (range) between any two WIRELESS INTERCONNECT Alarms is
typically 50 feet (15 meters) inside of a home. Some features of a home, such as the number
of floors, number/size of rooms, furniture and types of building materials used may reduce
the range of the Alarms. Examples include: suspended ceilings, ductwork, large metallic
appliances (refrigerators) and metal studs. A feature of WIRELESS INTERCONNECT Alarms is
that they operate as a mesh network. All Alarms will repeat any alarm signal that is received
to all other WIRELESS INTERCONNECT Alarms. Interference from structural conditions can
be overcome by adding additional Alarms to route the wireless signal around obstructions.
The range and proper operation of any wireless device will vary depending
on its surroundings. It is very important that each Alarm is tested individually
before and after installation to make sure that all Alarms respond properly.
The WIRELESS INTERCONNECT Alarms are not to be used outdoors or to transmit
between buildings. The Alarms will not communicate properly under these conditions.
Metal objects and metallic wallpaper may interfere with signals from wireless
Alarms. Alarms should be tested after changes to your home such as
remodeling, moving furniture, and with metal doors opened and closed.
Your First Alert
®
WIRELESS INTERCONNECT Smoke Alarm will automatically communicate
potential fires with all other First Alert
®
WIRELESS INTERCONNECT Smoke Alarms.
Changes or modifications not expressly approved by BRK Brands, Inc.
could void the user’s authority to operate the equipment.
HOW TO INSTALL THIS SMOKE ALARM
THE PARTS OF THIS SMOKE ALARM
TOOLS YOU WILL NEED:
This unit is designed to be mounted on the ceiling, or on the wall if necessary.
Pencil
Drill with 3/16” (5 mm) drill bit
Phillips screwdriver
Hammer
Pliers to activate optional “tamper-resistant” locking features
If you want to lock the battery drawer, or lock the Smoke Alarm to the mounting bracket,
please read the “Optional Locking Features” section before you begin installation.
1. Test/Silence button
2. Battery drawer
3. Power indicator LED
4. Smoke Alarm LED
FOLLOW THESE SIMPLE STEPS!
1. Hold base firmly and twist the mounting bracket counterclockwise to separate it from the base.
2. Hold the mounting bracket against the ceiling (or wall) so the vertical
mounting slot is aligned in the 12 o’clock position and trace around the
inside of the mounting slots (vertical and horizontal mounting).
3. Put the unit where it won’t get covered with dust when you drill the mounting holes.
4. Using a 3/16” (5 mm) drill bit, drill a hole through the center of the oval outlines you traced.
5. Insert the plastic screw anchors (in the plastic bag with screws) into the holes. Tap the screw
anchors gently with a hammer, if necessary, until they are flush with the ceiling or wall.
6. Line the mounting bracket up
over the plastic screw anchors.
7. Screw the mounting bracket
to the ceiling or wall through
the mounting slots using
the two screws provided.
8. Attach the Smoke Alarm to the mounting bracket. Line up the guides on
the alarm’s base with the guides on the mounting bracket. When guides are
lined up, turn the base clockwise (right) until it snaps into place.
NOTE: Once the Smoke Alarm is snapped onto the mounting bracket,
you can rotate the Smoke Alarm to adjust the alignment.
9. Test the Smoke Alarm. See “Weekly Testing.”
OPTIONAL LOCKING FEATURES
The optional locking features are designed to prevent unauthorized removal of the battery or alarm. It is not necessary to
activate the locks in single-family households where unauthorized battery or alarm removal is not a concern.
These Smoke Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the
Smoke Alarm to the mounting bracket. You can choose to use either feature independently, or use them both.
Tools you will need: Needle-nose pliers Standard flathead screwdriver.
Both locking features use locking pins, which are molded into the mounting bracket. Depending on which locking
features you use, remove one or both pins from the mounting bracket using needle-nose pliers.
Da
To permanently remove either locking pin, insert a flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.
TO LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment
until you activate the battery
and test the Smoke Alarm.
Da
If the unit does not alarm during testing,
DO NOT lock the battery compartment!
Install new batteries and test again.
If the Smoke Alarm still does not
alarm, replace it immediately.
1. Using needle-nose pliers, detach one
locking pin from the mounting bracket.
2. After batteries are inserted, then
push the locking pin through the
hole near the battery door latch on
the back of the Smoke Alarm.
TO LOCK THE MOUNTING BRACKET
1. Using needle-nose pliers or a
utility knife, detach one locking
pin from the mounting bracket.
2. Insert the locking pin through the
hole on the back of the Smoke
Alarm as shown in the diagram.
3. When you attach the Smoke
Alarm to the mounting bracket,
the locking pin’s head will fit
into a notch on the bracket.
TO UNLOCK THE BATTERY COMPARTMENT
1. Remove the Smoke Alarm from the mounting
bracket. If the unit is locked to the bracket, see
the section “To Unlock the Mounting Bracket.
2. Insert a flathead screwdriver under the head
of the locking pin, and gently pry it out of the
battery compartment lock. (If you plan to relock
the battery compartment, save the locking pin.)
3. To relock the battery compartment, close the
battery door and reinsert locking pin in lock.
4. Reattach the Smoke Alarm to the mounting bracket.
Da
When replacing the batteries, always
test the Smoke Alarm before relocking
the battery compartment.
TO UNLOCK THE MOUNTING BRACKET
1. Insert a flathead screwdriver into the
rectangular cut-out on the mounting
bracket nearest to the locking pin.
2. Pry the Smoke Alarm away from
the bracket by pushing up on
the screwdriver and turning the
Smoke Alarm counterclockwise
(left) at the same time.
WEEKLY TESTING
NEVER use an open flame of any kind to test this unit. You might accidentally
damage or set fire to the unit or to your home. The built-in test switch accurately
tests the unit’s operation as required by Underwriters Laboratories, Inc. (UL).
If the Alarm ever fails to test properly, replace it immediately. Products under warranty
may be returned to the manufacturer for replacement. See “Limited Warranty” for details.
DO NOT stand close to the alarm when the horn is sounding. Exposure at close range
may be harmful to your hearing. When testing, step away when horn starts sounding.
It is important to test this unit every week to make sure it is working properly.
Using the test button is the recommended way to test this Smoke Alarm. Press and hold
the test button on the cover of the unit until the alarm sounds (the unit may continue to
alarm for a few seconds after you release the button). If it does not alarm, make sure
the unit is receiving power (LED will flash approximately once a minute indicating it has
power); and test it again. If it still does not alarm, replace it immediately. During testing
you will hear a loud, repeating horn pattern: 3 beeps, pause, 3 beeps, pause.
REGULAR MAINTENANCE
This unit has been designed to be as maintenance free as possible, but there
are a few simple things you must do to keep it working properly.
Test it at least once a week.
Clean the Smoke Alarm at least once a month; gently vacuum off any dust using
your household vacuum’s soft brush attachment, and test the Smoke Alarm after
cleaning. Never use water, cleaners or solvents since they may damage the unit.
If the Smoke Alarm becomes contaminated by excessive dirt, dust and/or grime, and
cannot be cleaned to avoid unwanted alarms, replace the unit immediately.
Relocate the unit if it sounds frequent unwanted alarms. See
“Locations to Avoid For Smoke Alarms” for details.
When the battery becomes weak, the Smoke Alarm unit will “chirp” approximately once
a minute (the low battery warning). This low battery warning should last for up to 7
days, but you should replace the battery immediately to continue your protection.
Choosing a replacement battery:
Your Smoke Alarm requires 2 “AA” batteries: Energizer E91 or Duracell MN1500.
These batteries are available at many local retail stores.
Always use the exact batteries specified by this User’s Manual. DO NOT use
rechargeable batteries. Clean the battery contacts and also those of the device prior
to battery installation. Install batteries correctly with regard to polarity (+ and -).
Please dispose of or recycle used batteries properly, following any local
regulations. Consult your local waste management authority or recycling
organization to find an electronics recycling facility in your area. DO NOT
DISPOSE OF BATTERIES IN FIRE. BATTERIES MAY EXPLODE OR LEAK.
Keep battery out of reach of children. In the event a battery is swallowed,
immediately contact your poison control center, your physician, or the National
Battery Ingestion hotline at 202-625-3333 as serious injury may occur.
Actual service life depends on the Smoke Alarm and the environment in which it is installed.
All the batteries specified above are acceptable replacement batteries for this unit.
To replace the batteries (without removing
Alarm from the ceiling or wall):
1. Open the battery compartment.
2. Press tabs A and B as shown in the diagram and remove each battery.
3. Insert the new batteries, making sure they snap completely
into the battery compartment. Match the terminals on the
ends of the batteries with the terminals on the unit.
4. Close the battery compartment, and then test the
unit by pressing the Test/Silence button.
A
B
IF THIS SMOKE ALARM SOUNDS
RESPONDING TO AN ALARM
During an alarm, you will hear a loud, repeating horn pattern: 3 beeps,
pause, 3 beeps, pause. The red LED will flash rapidly.
If the unit alarms and you are not testing the unit, it is warning you of a
potentially dangerous situation that requires your immediate attention. NEVER
ignore any alarm. Ignoring the alarm may result in injury or death.
Never remove the batteries from a battery operated Smoke Alarm to stop an
unwanted alarm (caused by cooking smoke, etc.). Removing batteries disables
the alarm so it cannot sense smoke, and removes your protection. Instead open a
window or fan the smoke away from the unit. The alarm will reset automatically.
If the unit alarms get everyone out of the house immediately.
What To Do In Case Of Fire
Don’t panic; stay calm. Follow your family escape plan.
Get out of the house as quickly as possible. Don’t stop to get dressed or collect anything.
Feel doors with the back of your hand before opening them. If a door is cool, open it slowly.
Don’t open a hot door. Keep doors and windows closed, unless you must escape through them.
Cover your nose and mouth with a cloth (preferably damp). Take short, shallow breaths.
Meet at your planned meeting place outside your home, and do a
head count to make sure everybody got out safely.
Call the Fire Department as soon as possible from outside. Give your address, then your name.
Never go back inside a burning building for any reason.
Contact your Fire Department for ideas on making your home safer.
Alarms have various limitations. See “Limitations of Smoke Alarms” for details.
USING THE SILENCE FEATURE
The Silence Feature can temporarily quiet an unwanted alarm for up to 15 minutes. To use
this feature, press the “Push to Test/Silence” button on the cover. If the unit will not silence
and no heavy smoke is present, or if it stays in silence mode continuously, it should
be replaced immediately. The LED will continue to flash rapidly while in silence.
The Silence Feature does not disable the unit—it makes it temporarily less sensitive
to smoke. For your safety, if smoke around the unit is dense enough to suggest a
potentially dangerous situation, the unit will stay in alarm or may re-alarm quickly.
If you do not know the source of the smoke, do not assume it is an unwanted alarm.
Not responding to an alarm can result in property loss, injury, or death.
SILENCING THE LOW BATTERY WARNING
This silence feature can temporarily quiet the low battery warning “chirp” for up to 8 hours. You can
silence the low battery warning “chirp” by pressing the Test/Silence button on the alarm cover.
Once the low battery warning “chirp” silence feature is activated, the unit continues to flash the
Green light twice a minute for 8 hours. After 8 hours, the low battery “chirp” will resume. Replace
the batteries as soon as possible; this unit will not operate without battery power!
To deactivate this feature: Press the Test/Silence button again. The unit will go into Test Mode
and the low battery warning will resume (LED flashes and unit sounds “chirp” once a minute).
LATCHING FEATURES
Alarm Latch is activated after an Alarm is exposed to alarm levels of smoke. After
smoke levels drop below alarm levels, the Smoke” Red LED will begin to flash
On for 2 seconds/Off for 2 seconds. It will continue to flash or “latch” for about
15 minutes, to give you time to determine which unit initiated the alarm.
Low Battery Latch is activated when the Alarm is in the “low battery condition”. When this
occurs, the Power LED flashes Green On for 2 seconds/Off for 2 seconds for about 15 minutes.
This feature is designed to help you identify which Alarm needs to have the battery replaced.
Although, the Alarm will sound the low battery chirp approximately once every minute, sometimes
during the initial stages of “low battery”, the Alarm will chirp in greater intervals than one minute,
sometimes up to several hours, until the battery reaches a steady low battery level. This innovative
feature eliminates the frustration of waiting for and/or identifying which unit is chirping.
IF YOU SUSPECT A PROBLEM
Smoke Alarms may not operate properly because of dead, missing or weak batteries, a
build-up of dirt, dust or grease on the Smoke Alarm cover, or installation in an improper
location. Clean the Smoke Alarm as described in “Regular Maintenance,” and install a
fresh battery, then test the Smoke Alarm again. If it fails to test properly when you use
the test button, or if the problem persists, replace the Smoke Alarm immediately.
If you hear a “chirp” about once a minute, replace the battery.
If you experience frequent non-emergency alarms (like those caused
by cooking smoke), try relocating the Smoke Alarm.
If the alarm sounds when no smoke is visible, try cleaning or
relocating the Smoke Alarm. The cover may be dirty.
If the alarm does not sound during testing, try installing a new
battery, and make sure it is snapped in securely.
If the alarm sounds 3 rapid “chirps” every minute; LED flashes approximately once a
minute. MALFUNCTION: the device is not working properly and needs to be replaced.
Do not try fixing the alarm yourself – this will void your warranty!
If the Smoke Alarm is still not operating properly, and it is still under warranty,
please see “How to Obtain Warranty Service” in the Limited Warranty.
RECOMMENDED LOCATIONS FOR SMOKE ALARMS
Installing Smoke Alarms in Single-Family Residences
The National Fire Protection Association (NFPA), recommends one Smoke Alarm on every floor, in
every sleeping area, and in every bedroom. In new construction, the Smoke Alarms must be AC
powered and interconnected. See “Agency Placement Recommendations” for details. For additional
coverage, it is recommended that you install a Smoke Alarm in all rooms, halls, storage areas,
finished attics, and basements, where temperatures normally remain between 40˚ F (4.4˚ C) and 100˚ F
(37.8˚ C). Make sure no door or other obstruction could keep smoke from reaching the Smoke Alarms.
More specifically, install Smoke Alarms:
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep with doors closed.
In the hall near every sleeping area. If your home has multiple sleeping areas, install a
unit in each. If a hall is over 40 feet (12 meters) long, install an alarm at each end.
At the top of the first-to-second floor stairway, and at bottom of basement stairway.
Specific requirements for Smoke Alarm installation vary from state to state and from region
to region. Check with your local Fire Department for current requirements in your area. It
is recommended AC or AC/DC units be interconnected for added protection.
WIRELESS
INTERCONNECT
ALARMS
AGENCY PLACEMENT RECOMMENDATIONS
NFPA 72 Chapter 29
“For your information, the National Fire Alarm and Signaling Code, NFPA 72, reads as follows:”
29.5.1* Required Detection.
29.5.1.1* Where required by other governing laws, codes, or standards for a specific type of
occupancy, approved single and multiple-station smoke alarms shall be installed as follows:
(1) *In all sleeping rooms and guest rooms
(2) *Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any
door to a sleeping room, with the distance measured along a path of travel
(3) On every level of a dwelling unit, including basements
(4) On every level of a residential board and care occupancy (small facility),
including basements and excluding crawl spaces and unfinished attics
(5) *In the living area(s) of a guest suite
(6) In the living area(s) of a residential board and care occupancy (small facility)
(Reprinted with permission from NFPA 72
®
, National Fire Alarm and Signaling Code Copyright © 2010
National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete
and official position of the National Fire Protection Association, on the referenced subject which is
represented only by the standard in its entirety), (National Fire Alarm and Signaling Code
®
and NFPA
72
®
are registered trademarks of the National Fire Protection Association, Inc., Quincy, MA 02269).

Summary of content (2 pages)