Company UCQB Series Installation Manual

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
UCQ/UCXQ SERIES FAN COIL UNIT
GENERAL
The manufacturer assumes no respon-
sibility for equipment installed in viola-
tion of any code requirement.
These instructions give information
relative to the installation of UCQ fan coil
units only. For other related equipment
refer to the proper instructions.
Material in this shipment has been
inspected at the factory and released to
the transportation agency in good condi-
tion. When received, a visual inspection
of all cartons should be made immedi-
ately. Any evidence of rough handling or
apparent damage should be noted on
the delivery receipt and the material in-
spected in the presence of the carrier's
representative. If damage is found, a
claim should be filed against the carrier
immediately.
Note: State of MA.-248 CMR code of the
state of MA. requires a pump timer (60
seconds on every 6 hours). See dia-
gram.
FAN COIL UNIT
The installer must adhere strictly to all
local and national code requirements
pertaining to the installation of this
equipment.
These units are designed to be in-
stalled vertically in the upflow position by
the following mounting means:
Hung on closet wall
Using mounting kit 90PK3, air handler
may be wall mounted. Brackets and
screws are provided for both the closet
wall and the air handler.
It is recommended that sound isolat-
ing material be installed to prevent any
undesired transfer of sound.
Recessed in a wall
Installation of the fan coil recessed into
a partition wall with it's recommended
framing is shown in figure 1. Note: the
front face of the unit must be installed
flush with the dry wall. This application
requires the optional louvered wall
panel which must be ordered sepa-
rately. Wall panel with frame is secured
to the studs by screws or nails after the
dry wall has been installed. Refer to
figure 2 and 3.
Closet Platform Front Return
Fan coil is to be set on a platform and
secured by screws or nails. Sufficient
space for drain piping is required under
****** WARNING ******
Extreme caution must be
taken that no internal damage
will result if screws or holes are
drilled into the cabinet.
****** WARNING ******
Unit must not be operated
during building construction
due to excessive airborne dust
and debris. The unit must not
be operated under any
circumstances without an air
filter in place.
AIR DISTRIBUTION
DUCTS
All duct work must be installed in accor-
dance with National Fire Protection As-
sociation Codes 90A and 90B. Ducts
should be adequately insulated to pre-
vent condensation during the cooling
cycle and to minimize heat loss during
the heating cycle. All return air must be
filtered to prevent dirt buildup on the coil
surface. If there is no ducted return,
applicable installation codes may limit
the unit to installation only in a single
story residence. In many cases it is
acceptable to use ducting of the same
size as the fan coil connections. How-
ever, unique arrangements or long duct
runs must be confirmed by a local pro-
fessional. The manufacturer will not be
responsible for misapplied equipment.
the platform.
All fan coil units are U.L. Listed for
installation with zero inches clearance to
combustible materials. This includes
the fan coil cabinet, discharge plenum
and connecting ducts. Sufficient clear-
ance must be provided at the front of the
fan coil to allow access to electrical con-
trols and removal of the motor /blower
assembly for servicing. This clearance
distance should be approximately the
same as the depth dimension of the fan
coil unit.
L2463 3/11
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service
personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.
Current Maintenance Program is available at www.firstco.com under "Product Information".