Company HBC Series Spec Sheet
-20-
BLOWER PERFORMANCE
PHBC 220 VOLT/ 50Hz PSC
Product Specifications
Horizontal Fan Coils
2-Pipe/4-Pipe Hydronic
PSC MOTOR
PHBC (220 Volt / 50Hz)
CFM vs EXTERNAL STATIC PRESSURE (3 ROW 220 Volt)
MODEL HP
MAX
RPM
AMPS
(220V)
FAN
SPEED
EXTERNAL STATIC PRESSURE (inches of water)
0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.50
3*PHBC-3
1/20 1075 0.40
HI
MED
LOW
230
195
150
200
160
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4*PHBC-3
1/12 1050 0.55
HI
MED
LOW
420
350
275
380
305
230
335
265
200
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
5*PHBC-3
1/12 1050 0.55
HI
MED
LOW
410
340
270
365
295
230
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6*PHBC-3
1/5 1550 1.02
HI
MED
LOW
585
520
455
540
480
415
500
440
375
455
400
325
410
350
275
---
---
---
---
---
---
---
---
---
---
---
---
8*PHBC-3
1/5 1550 1.02
HI
MED
LOW
795
605
425
750
580
405
700
555
390
660
530
365
620
500
340
580
460
---
535
410
---
---
---
---
---
---
---
10*PHBC-3
1/4 1625 1.53
HI
MED
LOW
920
825
685
865
775
640
810
730
605
755
680
570
700
635
535
650
585
495
595
540
440
545
490
365
---
---
---
13*PHBC-3
1/5
(two)
1550
1.02
Ea.
HI
MED
LOW
1165
1050
855
1110
1000
815
1055
945
775
1000
890
730
935
825
680
860
760
625
775
680
555
680
580
465
---
---
---
CFM vs EXTERNAL STATIC PRESSURE (4 ROW or 3/1 Split 220 Volt)
3*PHBC-4
-31
1/20 1075 0.40
HI
MED
LOW
225
190
150
200
165
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4*PHBC-4
-31
1/12 1050 0.55
HI
MED
LOW
405
340
275
370
310
230
330
275
200
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
5*PHBC-4
-31
1/12 1050 0.55
HI
MED
LOW
410
330
270
365
290
225
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6*PHBC-4
-31
1/5 1550 1.02
HI
MED
LOW
585
520
455
545
480
415
505
440
370
460
395
325
410
345
280
355
295
225
---
---
---
---
---
---
---
---
---
8*PHBC-4
-31
1/5 1550 1.02
HI
MED
LOW
745
590
415
705
560
395
665
535
375
625
500
355
580
465
325
535
420
285
485
370
230
---
---
---
---
---
---
10*PHBC-4
-31
1/4 1625 1.53
HI
MED
LOW
865
785
665
815
735
630
770
695
595
725
650
560
675
610
520
625
570
475
570
520
420
---
---
---
---
---
---
13*PHBC-4
-31
1/5
(two)
1550
1.02
Ea.
HI
MED
LOW
1080
985
825
1020
930
785
965
870
740
905
810
685
835
745
625
760
665
555
670
585
475
---
---
---
---
---
---
CFM vs EXTERNAL STATIC PRESSURE (4/1 or 3/2 Split 220 Volt)
3*PHBC-41
-32
1/20 1075 0.40
HI
MED
LOW
225
190
145
195
160
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4*PHBC-41
-32
1/12 1050 0.55
HI
MED
LOW
395
330
260
355
295
215
315
260
170
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
5*PHBC-41
-32
1/12 1050 0.55
HI
MED
LOW
395
325
265
345
285
225
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6*PHBC-41
-32
1/5 1550 1.02
HI
MED
LOW
535
485
430
495
445
390
460
405
350
415
365
305
370
320
260
---
---
---
---
---
---
---
---
---
---
---
---
8*PHBC-41
-32
1/5 1550 1.02
HI
MED
LOW
740
590
420
700
560
400
660
530
380
615
500
360
575
470
330
525
430
300
---
---
---
---
---
---
---
---
---
10*PHBC-41
-32
1/4 1625 1.53
HI
MED
LOW
850
785
660
800
735
615
755
680
575
705
635
540
655
590
505
600
545
465
540
490
410
---
---
---
---
---
---
13*PHBC-41
-32
1/5
(two)
1550
1.02
Ea.
HI
MED
LOW
1030
950
800
975
895
755
920
835
705
860
775
650
790
705
595
715
630
530
630
550
455
---
---
---
---
---
---
Notes:
1. Motors are 220v / 50Hz,high
effciency PSC type
2. Maximum HACR breaker is
15 amp
3. coilns-per-inchvariesto
allowconsistentairow