13.5 Master and Slave Panels
With the iControl2 it is possible to have up to four remote control panels at one iGenerator. (One Master + three
Slave)
The standard iControl panel has the Art. No. 21.02.02.131P. This Panel has integrated termination resistors and is
the Master Panel.
The iControl2 Slave Panel has the Art. No. 21.02.02.132P. It is marked with a sticker „Slave Panel“ at the back side.
In a iControl system with Master and Slave panels, The Master must be the last one in the row, so that the
termination resistor is at the end of the FP-BUS.
The Slave Panel can not be used alone. The Slave Panels must be connected between the iControl controller (at the
iGenerator) and the Master Panel.
The Master Slave configuration can be used at iGenerators with software 2.3 at Controller and Panel.
All Panels (Master and Slave) has the Address „1“ as standard. The Address can be changed in the menu. Possible
are 1, 2, 3 and 4. Each Panel must have a unique address.
To use the automatic start option, the connection of the automatic start must be at the panel with the address „1“.
Activation or deactivation can be done at every panel.
Fig. 13.5-1: Master Slave configuration
1
PandaiControl 2MasterͲSlaveͲBetrieb
Up to four Panelwork parallel.TheMasterPanel(21.02.02.131P)mustbe the lastPanelinthe row,sothat the
termination resistor is atthe end.Please label the cabels according to this.