10.9 Installation of the PMGi
The PMGi must be mounted vertical, with the electrical connection down. So you can read the writing on the PMGi.
The surface where the PMGi is mounted should be smoothed and support the heat transfer. The Air holes and Air
grille must be not covered and enough cooling air must be pleasant at any time for the PMGi.
To mount the PMGi use the fixing holes diameter 6,5mm.
Note!See the safety instruction in your Generator and iControl
Manual.
The rules of the respective regional authority must be adhered to. Only an electrician may carry out installation of the
electrical connections for safety reasons.
10.9.1 Electrical connection.
Only special trained persons are allowed to make the electrical connection.
When an extension cable is required, be sure to use a though rubber sheeted flexible and fireproof cable. Limit
length of extension cables depends on the voltage drop along the cable. This drop must be less than 2,5 % value of
the nominal output voltage.
Pay attention to the right pin assignment. See “Socket pins of the PMGi 5000” on page 93.
10.9.1.1 Connection to a system with RCD
The PMGi is prepared for the use in a RCD protected grid.,
The PMGi out must be connected 1:1 (PE,N,L) to the customers electrical cabinet. The Life wire and neutral wire will
be connected to the RCD. The PE will be connected to the PE of the electrical cabinet. After installation the function
of the RCD must be tested.