Product Manual

- 10 -
COMBUSTION AIR ADJUSTMENTS:
NOTE: Proper combustion air adjustment must be achieved using a certified
combustion analyzer to ensure complete combustion.
The air adjustment should be made to achieve 10% CO
2
on natural gas and
12% CO
2
on propane.
SETTING THE AIR ADJUSTMENT PLATE
A) Regulation of the combustion air flow is made by adjustment of the manual AIR
ADJUSTMENT PLATE (1) after loosening the FIXING SCREWS (2 and 3). The initial
setting of the air adjustment plate should be made according to Column 5 in the Burner
Set-up Chart.
B) The proper number on the manual AIR
ADJUSTMENT PLATE (1) should line up with the
SETTING INDICATOR (4) on the fan housing
cover. Once set, the air adjustment plate should be
secured in place by tightening SCREWS 2 and 3.
C) The final position of the air adjustment
plate will
vary on each installation. Use instruments to
establish the proper settings for maximum CO
2
.
NOTE: Variations in flue gas, CO
2
and
temperature readings may be experienced when the
burner cover is put in place. Therefore, the burner cover must be in place when making
the final combustion instrument readings, to ensure proper test results.
BURNER SET-UP CHART
1 2 3 4 5
FIRING RATE
(BTUH)
ORIFICE-LP
ORIFICE-NG
HEAD
SETTING
AIR DAMPER
SETTING
200,000
PART #
FVP-225
PART #
FVN-226
5
3 LP
3.8 NG