Installation Guide
04.4.2018 | Page 3
Flexco Floors | 1401 E. 6th St. - Tuscumbia, AL 35674 
P: 800.633.3151 | excooors.com | Made in the USA
TECHNICAL DATA SHEET
VINYL STAIR TREADS, RISERS & STRINGERS
Vinyl Treads
spikes. Do not allow product to be directly 
exposed to extreme heat sources, such 
as radiators, ovens or other high-heat 
equipment. May be susceptible to staining 
from harsh disinfectants, cleaning agents, 
dyes or other harsh chemicals – ensure all 
chemicals and materials that may come 
in contact with stair treads, risers or 
stringers will not stain, mar or otherwise 
damage the material prior to use.
SUBSTRATE PREPARATION
All substrates must be prepared according 
to ASTM F710, as well as applicable ACI 
and RFCI guidelines. Substrates must 
clean, smooth, permanently dry, flat, and 
structurally sound. Substrates must be 
free of visible water or moisture, dust, 
sealers, paint, sweeping compounds, 
curing compounds, residual adhesives 
and adhesive removers, concrete 
hardeners or densifiers, solvents, wax, 
oil, grease, asphalt, visible alkaline salts 
or excessive efflorescence, mold, mildew 
and any other extraneous coating, film, 
material or foreign matter. 
All substrates must have any and all existing 
adhesives, materials, contaminants or 
bond-breakers mechanically removed via 
scraping, sanding or grinding. Mechanical 
preparation must expose at least 90% 
of the original substrate. Following 
cleaning and removal, all substrates 
must be vacuumed with a flat vacuum 
attachment or damp mopped with clean, 
potable water to remove all surface dust. 
Sweeping without vacuuming or damp 
mopping will not be acceptable. 
All porous substrates must be tested per 
ASTM F3191 to confirm porosity. Use a 
pipette or equivalent to conduct three 
tests by placing a .05 mL (1/4” wide) 
droplet of clean, potable water onto the 
surface. If the substrate absorbs water 
within 60 seconds, the substrate is 
considered porous. Conduct 3 tests for 
the first 3000 sq. ft. and one for each 
additional 2000 sq. ft., at least one per 
room. All other substrates that do not 
meet this requirement are considered 
non-porous. Ensure that all non-porous 
substrates are not contaminated with any 
aforementioned contaminates.
It is recommended that all substrates 
have a floor flatness of FF32 and/or a 
flatness tolerance of 1/8” in 6’ or 3/16” 
in 10’. Substrates that do not meet this 
requirement should have a compatible 
cementitious patch (such as the Excelsior 
CP-300) or self-leveling underlayment 
(such as the Excelsior SU-310) installed to 
flatten the installation area.
Do not use solvent/citrus based adhesive 
removers prior to installation. Follow 
The Resilient Floor Covering Institute’s 
(RFCI) “Recommended Work Practice for 
Removal of Existing Floor Covering and 
Adhesive”, and all applicable local, state, 
federal and industry regulations and 
guidelines. When removing asbestos and 
asbestos containing materials, follow all 
applicable OSHA standards.
CONCRETE SUBSTRATES
All concrete must have a minimum 
compressive strength of 3500 PSI and 
be prepared in accordance with ASTM 
F710. When flooring is being installed 
directly over concrete, concrete surfaces 
that have an ICRI Concrete Surface Profile 
(CSP) over 4 should be flattened with a 
self-leveling underlayment or a patch to 
prevent imperfections from telegraphing 
through flooring materials. On or below 
grade concrete must have a permanent, 
effective moisture vapor retarder installed 
below the slab. 
New or existing concrete substrates on all 
grade levels must be tested in accordance 
with ASTM F2170, using in situ Probes, to 
quantitatively determine the amount of 
relative humidity no more than one week 
prior to the installation. 
If ASTM F2170 test results exceed the 
prescribed limits, a moisture mitigation 
product, such as Excelsior MM-100 
Moisture Mitigation, must be installed 
prior to proceeding with installation. 
Install The MM-100 per technical data 
  Adhesive RH Limits
AW-510 Acrylic Wet-Set: 90% RH
TP-620 Tape Adhesive: 80% RH
C-630 Contact Adhesive: 85% RH
MS-700 Modified Silane: 95% RH
EW-710 Epoxy Wet-Set: 90% RH
1.  PRE-INSTALLATION CHECKLIST
•  Consult all associated product 
literature concerning adhesive 
installation, maintenance and 
warranty prior to installation of 
flooring.
•  Allow all trades to complete work 
prior to installation.
•  Deliver all materials to the installation 
location in its original packaging with 
labels intact.
•  Do not stack pallets to avoid damage.
•  Remove any plastic and strapping 
from product after delivery.
•  Inspect all material for proper type, 
color and matching lot numbers if 
appropriate.
•  Ensure that all adhesives intended 
for installation are approved for use 
with stair tread, riser and/or stringer 
material.
•  Ensure installation area and material 
storage temperatures are between 
65° F (19° C) and 85° F (30° C) for 
at least 48 hours before, during and 
after installation. 
•  Ensure HVAC system is operational 
and fully functioning at normal 
operating conditions.
•  Protect installation area from extreme 
temperature changes, such as heat 
and freezing, as well as direct sunlight 
for at least 48 hours before, during 
and after installation. 
•  Ensure all substrate preparation 
and moisture testing requirements 
have been performed, read and/or 
understood by all interested parties. 
•  Do not proceed with installation until 
all conditions have been met.
2.  PRODUCT LIMITATIONS
Do not install materials over LVT, 
cushioned vinyl, hardwood flooring, 
cork, rubber, or asphaltic materials. 
Do not install stair tread materials in 
outdoor areas, residences, in or around 
commercial kitchens or areas that may 
be exposed to animal or vegetable fats 
and oils, grease and petroleum-based 
hydrocarbons. Do not install in areas 
that may be subjected to sharp, pointed 
objects, such as stiletto heels, cleats or 








