Installation Guide

09.12.2017 | Page 7
Flexco Floors | 1401 E. 6th St. - Tuscumbia, AL 35674
P: 800.633.3151 | flexcofloors.com | Made in the USA
TECHNICAL DATA SHEET
STATIC CONTROL TILE
ESD Vinyl
A
B
C
A. Specific and/or customized ESD grounding system, such as a grounding bar, typically built
into facility. Contact electrical or facility representative for detail.
B. Steel building column or grounded building framing system. Grounding lug fastened to steel
framing per NEC requirements (see Method B Detail below).
C. Standard copper connection, typically routed to an electrical system ground connection from
a receptacle box (see Method C Detail below).
Method B Detail
Steel building frame
Electrical lug, mechanically fastened to steel
frame for connection to copper grounding
strap.
18" copper grounding strap, with 9" of strap
embedded in adhesive.
ESD Vinyl tile.
Method C Detail
Receptacle box.
Conduit coupling.
Receptacle box grounding connection.
#12 awg copper wire, routed from receptacle
box grounding connection, to electrical lug and
then to electrical system ground.
Electrical lug, mechanically fastened to
receptacle box for connection to copper
grounding strap.
18" copper grounding strap.
Green ground wire.
Electrical
system
ground
ESD VINYL DIAGRAMS & DETAILS
ASD-800 or USD-810, installed above
and below grounding strap.
18" copper grounding strap,
with 9" of strap embedded in
adhesive.
ESD Vinyl tile.
Connect remaining copper grounding strap to
acceptable grounding system.
Copper Grounding
Strap Installation
Acceptable ESD Grounding Systems & Methods