modulating valve to maintain desired discharge temperature.
Additional Sequence of Operation All VFD Motor Control
1. During lower speeds, the low-speed potentiometer increases the resistance going to the modulating
valve to limit temperature rise.
2. VFD contacts are included in the burner control circuit to disable the burner should a fault condition
occur in the VFD.
VFD by Others and VAV Choke Off Profile Bypass Damper
As the VFD increases and decreases speed the profile air flow switch modulates the VAV bypass
damper motor to maintain proper pressure drop across the burner profile.
Factory VFD Profile Bypass Damper
The VFD produces a 0-10vdc or a 4-20ma signal to the profile damper motor which modulates
the profile damper’s opening to maintain the burner profile pressure drop. The range of this
modulation must coincide with the VFD operating range.
VFD Preset Speeds
1. Inputs are made to the VFD to engage programmable pre-set speeds. A factory-supplied VFD wiring
and programming instruction sheet comes with every unit. Consult the as-built schematics and the
VFD manual for additional information.
Manual Potentiometer Adjustment – VFD and Choke-Off Dampers
1. A 10k-15k ohm potentiometer may be field supplied and installed if remote manual control is required
for the VFD. See VFD manual for proper installation.
2. A 135 ohm potentiometer is used for remote manual control of choke-off vav dampers.
Static Pressure Control (Photohelic) – VFD and Choke-Off Dampers
The VFD or Choke-off dampers can be controlled by a building static pressure control. This controller will
sense the difference between pressure inside the building, and pressure outside the building and will
control the operating speed of the VFD or position of choke-off dampers to maintain the pressure setting
on the controller. The controller has two set points and an indicator. The two set points are a minimum
desired static pressure point, and a maximum static pressure point.
When building static pressure is below the minimum setting, the VFD will increase the blower RPM or
choke-off damper will open to increase airflow. If the building static is above maximum setting, the VFD
will decrease the blower RPM or close choke-off dampers. When building static pressure is between the
minimum and maximum settings, no signal is given to change VFD speed or choke-off damper position.
See additional wiring and installation information on the static pressure controller and outdoor sensor.
The static pressure controller can be ordered to be shipped loose or mounted inside the unit to reduce
field wiring and assembly.