User manual
Application Software
Upload / Download (2638A and 1586A)
Use the Digital I/O Points Communication Dialog
Use the Digital I/O Points Communication dialog to set
any of the relays or DIO pins active when an alarm
condition occurs in the channel. Status of all of the relays
and DIO pins can also be viewed and IO bits and relays
can be set or cleared.
• Bits or relays that are set show a green dot.
• Bits or relays set by an alarm have a red dot.
• A bit set by an external signal has a blue dot.
There is no way to set a relay externally. When a relay is
set, it has closed contacts. When a bit is set, it has a logic
low signal (also called active low).
To view the digital I/O points dialog:
1. Click
on the Software toolbar.
2. Highlight an I/O module in the TreeView panel and
the Digital I/O Points dialog is shown.
41