User's Manual

150X Series
Calibration Manual
18
Table 5. Insulation Resistance Accuracy Test
Display Reading Limits
Step
Insulation
Voltage Range
Applied Display Units
1503 1507/1508
1 1000 V 9 GΩ N/A 7.8 to 10.2
2 1000 V 1.9 GΩ 1862 to 1938 N/A
3 1000 V 1 MΩ 0.5 to 1.5 0.5 to 1.5
4 1000 V 49 MΩ 47.5 to 50.5 47.8 to 50.2
5 1000 V 60 MΩ 58.3 to 61.7 58.6 to 61.4
6 500 V 500 kΩ 0.44 to 0.56 0.44 to 0.56
7 250 V 250 kΩ N/A 0.20 to 0.30
8 100 V 100 kΩ N/A 0.6 to 0.15
9 50 V 50 kΩ
MΩ
N/A 0.0 to 0.10
Insulation Function, External Sense
The following test verifies that the Tester will sense a voltage > 30 V when present on the
circuit under test.
1. Connect the UUT
INSULATION and COM output terminals to the Fluke 5320A
voltage output terminals.
2. Set the 5320A to the voltage output function (V).
3. Turn the UUT rotary function switch to an insulation function.
4. Apply 35 V, 50 Hz to the UUT.
5. Verify that the UUT displays > 30 V in the primary display, and the red LED
lightning bolt comes on.
Source Voltage Accuracy Test, "R" Nominal
Complete the test steps in Table 6 to verify source voltage of the insulation function
under load. If using the Fluke 5320A, use the high resistance function to verify source
voltage.
1. Connect the Fluke 5320A high resistance output terminals to the UUT
INSULATION and COM terminals.
2. Put the Fluke 5320A in the high resistance function (H).
3. Set the Fluke 5320A for the applied load shown in Table 6 for Steps 1-5.
4. Press T and verify that the UUT and Fluke 5320A voltage readings are
within the limits of Table 6. Record both of these readings.
5. Using the Fluke 5320A voltage reading as the reference, calculate the UUT
voltage reading error %, (5320A V - UUT V / 5320A V) x 100, and record for
later use.