Data Sheet

3 Fluke Corporation 1587/1577 Insulation Multimeters
DC millivolts measurement
Range Resolution Accuracy 1587 Accuracy 1577
600.0 mV dc 0.1 mV ± (0.1 % + 1) ± (0.2 % + 1)
DC and ac current measurement
Range Resolution
Accuracy 1587
± (% of Rdg+Digits)
Accuracy 1577
± (% of Rdg+Digits)
Burden Voltage
(Typical)
AC
45 to 1000 Hz
400 mA 0.1 mA ± (1.5 % + 2)
1
± (2 % + 2)
1
2 mV/mA
60 mA 0.01 mA ± (1.5 % + 2)
1
± (2 % + 2)
1
DC 400 mA 0.1 mA ± (0.2 % + 2) ± (1.0 % + 2) 2 mV/mA
60 mA 0.01 mA ± (0.2 % + 2) ± (1.0 % + 2)
1
1 kHz bandwidth
Overload: 600 mA for 2 minutes maximum
Overload protection: 440 mA, 1000 V, FAST fuse
AC conversion: Inputs are ac-coupled and calibrated to the rms value of sine wave input. Conversions are
true-rms responding and specified from 5 % to 100 % of range. Input signal crest factor can be up to 3 at
up to 300 mA, decreasing linearly to crest factor <
=
1.5 at 600 mA. For non-sinusoidal waveforms add
+ (2 % reading + 2 % FS) typical, for a crest factor up to 3.
Ohms measurement
Range Resolution Accuracy 1587
1
± (% of Rdg+Digits) Accuracy 1577
1
± (% of Rdg+Digits)
600.0 Ω 0.1
± (0.9 % + 2) ± (1.2 % + 2)
6.000 kΩ 0.001 k
60.00 k 0.01 k
600.0 k 0.1 k
6.000 MΩ 0.001 M
50.0 M
2
0.01 M ± (1.5 % + 3) ± (2.0 % + 3)
1
Accuracies apply from 0 to 100 % of range
2
Up to 80 % relative humidity
Overload protection: 1000 V rms or dc
Open circuit test voltage: < 8.0 V dc
Short circuit current: < 1.1 mA
Diode test (1587 Only)
Diode test indication: Display voltage drop: 0.6 V at 1.0 mA nominal test current
Accuracy: + (2 % + 3)
Continuity test
Continuity indication: Continuous audible tone for test resistance below 25 Ω and off above 100 Ω.
Maximum reading; 1000 Ω
Open circuit voltage: < 8.0 V
Short circuit current: 1.0 mA typical
Overload protection: 1000 V rms
Response time: > 1 m sec
Frequency measurement (1587 only)
Range Resolution Accuracy ± (% of Rdg+Digits)
99.99 Hz 0.01 Hz ± (0.1 % + 1)
999.9 Hz 0.1 Hz ± (0.1 % + 1)
9.999 kHz 0.001 kHz ± (0.1 % + 1)
99.99 kHz 0.01 kHz ± (0.1 % + 1)