User manual

Earth Ground Tester
Features
9
Resistance Limit Mode
The Tester has a resistance limit mode that allows you to set a maximum
resistance reading. If a resistance reading exceeds the set limit, the Tester
beeps and the >LIMIT icon displays. The limit can be set between 0 and
1999 Ω.
To set the maximum resistance:
1. Set the rotary switch to LIMIT. If the limit mode is on, the Tester
displays the stored limit setting. If the limit mode is off, the Tester
displays OFF.
2. If the limit mode is off, press START. The Tester displays the stored
limit setting.
3. Press DISPLAY to step through the digits to select the digit that you
want to set. The first press of DISPLAY selects the leftmost digit.
(The digit flashes when selected.) The second and third press of
DISPLAY selects the second and third digits. The fourth press of
DISPLAY selects the decimal point to set the resolution of the
measurement.
4. With the digit selected that you want to set, press START to
increment the value. The leftmost digit increments from 0 to 19. The
other digits increment from 0 to 9. Or if you selected the decimal
point, press START to move the decimal point to change the
resolution of the measurement.
5. Repeat steps 3 and 4 until you have set the maximum resistance
value. When you have finished, set the rotary switch to OFF for 5
seconds to store the value.