User's Manual
Table Of Contents
- Table of Contents
- General Aspects
- About This Manual
- Features of Fluke 434-II/435-II/437-II
- Basic Operations and Menu Navigation
- Display Information
- Input Connections
- Scope Waveform and Phasor
- Volts/Amps/Hertz
- Dips & Swells
- Harmonics
- Power & Energy
- Energy Loss Calculator
- Power Inverter Efficiency
- Unbalance
- Inrush
- Monitor - Power Quality Monitoring
- Flicker
- Transients
- Power Wave
- Mains Signaling
- Logger
- Shipboard V/A/Hz
- Cursor and Zoom
- Setting up the Analyzer
- Using Memory and PC
- Tips and Maintenance
- Specifications
- Appendices
- Index
Fluke 434-II/435-II/437-II
Users Manual
27-10
GENERAL
Case, Display, Memory, Real-time clock
Case Design Rugged, shock proof with integrated protective holster.
Drip and dust proof IP51 according to IEC60529 when used in tilt stand
position. The IP rating refers to non-operation of the Product and does not
indicate that the Product should be used around hazardous voltages in wet
environments. Shock and vibration: Shock 30 g, vibration 3 g sinusoid, random
0.03 g
2
/Hz according to MIL-PRF-28800F Class 2.
Display Brightness: 200 cd/m
2
typ. using power adapter, 90 cd/m
2
typical using battery
power.
Size 127 mm x 88 mm (153 mm/6.0 inch diagonal) LCD.
Resolution 320 x 240 pixels.
Contrast and brightness User-adjustable, temperature compensated.
Memory 8 GB SD-Card standard, upto 32 GB optionally.
Screen save and multiple data memories for storing data including recordings
(dependent on memory size).
Real-time clock Time and date stamp for Trend mode, Transient display, System Monitor and
event capture.
Environmental
Operating temperature 0 °C ... +40 °C; +40 °C ... +50 °C excl. battery
Storage temperature -20 °C ... +60 °C
Humidity +10 °C ... +30 °C: 95 % RH non-condensing;
+30 °C ... +40 °C: 75 % RH non-condensing;
+40 °C ... +50 °C: 45 % RH non-condensing.
Maximum operating altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V;
up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V;
Maximum storage altitude 12 km (40,000 ft).
Electro-Magnetic-Compatibility
(EMC)
EN 61326 (2005-12) for emission and immunity.
Interfaces mini-USB-B , Isolated USB port for PC connectivity
SD-card slot accessable behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on
accessories.
MECHANICAL
Size 265 x 190 x 70 mm
Weight 2kg including standard battery