Application Note
Application Note
Commercial buildings commonly
have a 208/120 V transformer in
a delta-wye configuration to
feed receptacles. Single-phase,
non-linear loads connected to
the receptacles produce triplen
harmonics, which add up in the
neutral. When this neutral cur-
rent reaches the transformer, it is
reflected into the delta primary
winding where it causes over-
heating and transformer failures.
Another transformer problem
results from core loss and copper
loss. Transformers are normally
rated for a 60 Hz phase current
load only. Higher frequency har-
monic currents cause increased
core loss due to eddy currents
and hysteresis, resulting in more
heating than would occur at the
same 60 Hz current.
Transformers supplying non-
linear loads should be checked
periodically to verify operation
within acceptable limits. Trans-
formers are also critical to the
integrity of the grounding system.
Factors
1. Transformer loading (kVA)
Start by measuring kVA and
determine wether the transformer
load is balanced.
•
Connect voltage probes on
Phase 1 and Neutral and
clamp current probe on same
phase. Repeat for Phase 2 and
3.
•
Use a single phase power
quality analyzer to read kVA of
each phase and sum all three
for total transformer kVA.
•
Or, connect all four current
clamps and all five test leads
for the three phase power
quality analyzer to read kVA
for each phase and the total.
From the Fluke Digital Library @ www.fluke.com/library
Common power
quality factors
affecting transformers
Unbalanced load:
kVA
TOTAL
= kVA
1
+ kVA
2
+ kVA
3
kVA
1
Red
Red
Red
Black
Black
Black
kVA
2
kVA
3
ø1
ø2
ø3
N
•
Compare actual load kVA to
nameplate kVA rating to deter-
mine % loading.
When using a single phase
analyzer on a balanced load, a
single measurement is suffic
ient.
Transformers loaded at less than
50 % are generally safe from
overheating. However, as loads
increase, measurements should
be made periodically. At some
point the transformer may require
derating.
2. Harmonic spectrum
The harmonic spectrum of the
secondary (load) current will give
us an idea of the harmonic orders
and amplitudes present:
•
In a transformer feeding sin
-
gle-phase loads, the principal
harmonic of c
onc
er
n is the
3rd
. The 3rd w
ill add arith-
metically in the neutral and
c
irculate in the delta primar
y
of a delta-w
ye transformer
.
The good news is that the
delta-w
ye tends to isolate the
rest of the system from the 3rd
(though not the 5th, 7th or
other non-triplen harmonics).
The bad new
s is that the
transformer pa
ys the pric
e
w
ith additional heat
.
Figur
e 1
. Measuring transformer load (unbalanc
ed) using a single phase power quality analy
zer
.
Figure 2. Harmonic spectrum.