Application Note

Application Note
Lighting is a major load for many large facilities.
Evaluating these circuits is important for both
energy conservation and power quality. Keep in
mind that commercial lighting loads are wired single
phase, with the loads connected from phase to
neutral. Typically, the phase-to-phase voltage is
480 V, with the phase-to-neutral voltage at 277 V.
Measurements must be taken at the lighting panel,
on all phases, since power consumption and Power
Factor could vary on each phase.
1. Power consumption
Excessive phase unbalance can
cause voltage unbalance, which
in turn can affect three-phase
motor loads. For example, in this
three-phase reading, phase A is
considerably higher than B and
C, when all three phases should
be equal.
From the Fluke Digital Library @ www.fluke.com/library
Troubleshooting
commercial
lighting loads
Measurements on commercial lighting loads
Measurement
L
ook for
1. Power consumption (kW) Balance among three phases.
2. P
ow
er F
actor (DPF and PF)
Mag
netic ballast w
ill ha
ve low DPF. Electronic ballast may have low total PF, although new
generations of ballast often ha
ve harmonic mitigation built-in
.
3. T
otal Harmonic Distortion (%THD)
Current %T
HD <20 % is desirable.
4. Voltage Stability Unstable voltage can cause lights to flicker.
2. Power Factor
Ballast with low PF might have
lower cost-of-purchase but
higher cost-of-operation. This
phasor diagram illustrates the
unbalance along with the power
factor.
3. Total Harmonic Distortion
Current THD should be consid-
ered when selecting ballast,
especially if there is a possibility
of transformer overloading. The
bar graph pinpoints the 5th and
7th harmonics as the larger
contributors.

Summary of content (2 pages)