Application Note

6 Fluke Corporation Checking ground electrode impedance for commercial, industrial and residental buildings.
The Selective Method
The Selective Method is a variation of the
Fall-of-Potential method, available on high-end
ground testers like the Fluke 1625. Testers with
this capability can measure the ground impedance
of a specific ground electrode without disconnect-
ing it from an array or from a structure’s distribu-
tion system. This means you don’t have to wait
for a shutdown to test or risk the safety hazards of
disconnecting the electrode from a live system.
The same rules for current stake and potential
stake placement apply as with Fall-of-Poten-
tial. If the conditions are met for the 62 % rule
(see previous page) then it can help reduce the
number of measurements. Otherwise it’s a good
idea to build a complete Fall-of-Potential plot. You
can use the Tagg Slope Technique if your curve
does not flatten out.
Both the Fall-of-Potential method and the
Selective Method use stakes to inject current and
measure voltage drop. The big difference is that
selective testing can accurately measure the test
current in the electrode under test.
The utility neutral, building steel and ground
electrode are all bonded and grounded. When
you inject a current into this system of paral-
lel ground connections the current will divide.
In a traditional Fall-of-Potential test you have
no way of knowing how much current is flow-
ing between any
particular electrode
and the C2 current
stake. Selective
testing uses an
integrated, high
sensitivity clamp-on
current transformer
to measure the
test current in the
electrode under
test. Figure 8 shows
how the current
transformer fits into
the test circuit. The
selective ground
tester digitally
filters the current
measurement to
minimize the effects
of stray currents.
Being able to
accurately measure
the current in the
electrode under test
effectively isolates
the electrode and
allows us to test
it without discon-
necting it from the
system or from
other electrodes.
#
(
0
0
#
3
%
EXT
34!24
$)30,!9
#(!.'%
/&&
2
!
2
3%,%#4
POLE POLE
POLE
'ROUND
2ESISTANCEK
!#2ESISTANCE
K
3!452.'%/
./2-!%ARTH'ROUND4ESTER
%LECTRODE
UNDERTEST
0ROBE
!UXEARTHELECTRODE
-ORETHANFT
-ORETHANFT
0 #
Stakeless or Clamp-on Method
The “stakeless” or “clamp-on” method allows
you to measure the impedance of a series loop of
ground electrodes. The test is simple and it may be
performed on an electrode that is connected to a
working electric service.
To make the measurement the tester uses a
special transformer to generate a voltage on the
ground conductor at a unique test frequency. It
uses a second transformer to distinguish the test
frequency and measure the resulting current
through the circuit.
This method is available in some Fall-of-Potential
testers (like the Fluke 1625) or in a single clamp on
unit. Figure 9 shows the connection of the source
and measure clamps of the Fluke 1625.
Figure 10 (see next page) shows the equivalent
test circuit for the stakeless method. When you test
a building ground electrode using this method, you
are actually testing a loop including:
Electrode under test
Ground electrode conductor
The main bonding jumper
The service neutral
Utility neutral-to-ground bond
Utility ground conductors (between poles)
Utility pole grounds
Because this method uses the service as part of
the circuit, it may be used only after the service has
been completely wired, that is, it cannot be used
prior to hook-up to the utility. In this method the
clamp checks the continuity of the interconnections
of all of the components above. An abnormally high
reading or an open circuit indication on the instru-
ment points to a poor connection between two or
more of the aforementioned critical components.
Figure 7: Connections for selective ground electrode
measurement
Figure 8: Connections for selective Electrode Impedance Mesaurement
#
(
0
0
#
3
%
EXT
34!24
$)30,!9
#(!.'%
/&&
2
!
2
3%,%#4
POLE POLE
POLE
'ROUND
2ESISTANCEK
!#2ESISTANCE
K
3!452.'%/
./2-!%ARTH'ROUND4ESTER
IN
'ROUNDING
%LECTRODE
#ONDUCTOR
Figure 9: Connecting the Saturn GEO X for a stakeless
measurement