Datasheet

Overvoltage
category In brief Examples
CAT IV Three-phase at
utility connection,
any outdoor
conductors
Refers to the “origin of installation, that
is, where low-voltage connection is made
to utility power
Electricity meters, primary overcurrent
protection equipment
Outside and service entrance, service
drop from pole to building, run between
meter and panel
Overhead line to detached building,
underground line to well pump
CAT III Three-phase
distribution,
including single-
phase commercial
lighting
Equipment in fixed installations, such as
switchgear and polyphase motors
Bus and feeder in industrial plants
Feeders and short branch circuits,
distribution panel devices
Lighting systems in larger buildings
Appliance outlets with short connections
to service entrance
CAT II Single-phase
receptacle
connected loads
Appliance, portable tools, and other
household and similar loads
Outlet and long branch circuits
Outlets at more than 10 meters (30 feet)
from CAT III source
Outlets at more that 20 meters (60 feet)
from CAT IV source
CAT I Electronic
Protected electronic equipment
Equipment connected to (source) circuits
in which measures are taken to limit
transient overvoltages to an appropriately
low level
Any high-voltage, low-energy source
derived from a high-winding resistance
transformer, such as the high-voltage
section of a copier
Table 1. Overvoltage installation categories. IEC 61010 applies to low-voltage
(< 1000 V) test equipment.
Built to with-
stand harsh
environments
with the highest
safety ratings
Rated all the way to CAT IV
ScopeMeter
®
test tools are rugged
solutions built for industrial troubleshoot-
ing. The new Fluke 190 Series II are
double-insulated floating oscilloscopes
safety rated for measurements in CATIII
1000V / CAT IV 600V environments.
Measure from mV to kV safely
Independent isolated inputs allow you
to make measurements in mixed circuits
having different ground references reduc-
ing the risk of accidental short circuits.
Conventional bench oscilloscopes with-
out special differential probes and isolation
transformers can only reference measure-
ments to line power earth ground.
With standard probes that cover a wide
application range from mV to kV, you’re
ready for anything from microelectronics to
heavy-duty higher voltage electrical appli-
cations.
IP-51 rated for harsh
environments
Rugged and shock-proof, ScopeMeter
®
portable oscilloscopes are built for dirty,
hazardous environments. With its sealed
case, it can endure
dust, drips, humidity
and airborne pollutants. Every time you
reach for ScopeMeter
®
portable oscillo-
scope you can be confident it will work
reliably wherever your work takes you.
33