Owner's Manual

Horizon 1000R/N Ice Machines 5
Speci cations
Electrical
Separate circuit and equipment ground required.
Evaporator unit
Standard electrical – 115/60/1
Maximum fuse – 15A
Amperage – 6A
Condensing unit
Single-Phase 3-Phase
Electrical 208-230 V, 60 Hz 208-230 V, 60 Hz
Maximum Circuit HVACR breaker size 15A 15A
Minimum Circuit Ampacity 10.7A 9.9A
Evaporator plumbing
3/8" OD push-in water inlet
3/4" MPT
Notes: 3/4" vented drain line must slope a minimum of 1/4" per ft (6 mm per 30.4 cm run).
Drain to be hard piped and insulated.
Water shut-off recommended within 10 ft (3 m).
Follett recommends installation of Follett water  lter system (P/N 00130286) in ice machine inlet water line.
Ambient
Evaporator unit
Air temperature 100 F/38 C max. 50 F/10 C min.
Water temperature 90 F/32 C max. 45 F/7 C min.
Water pressure 70 psi max. (483 kPa) 10 psi min. (69 kPa)
Condenser unit
Air temperature 120 F/49 C max. -20 F/-29 C min.
Refrigeration
3/8" liquid line – insulated
5/8" suction line – insulated
Note: Rack system installations require a capacity of 7,700 BTU/hr at 0 F (-18 C) evaporator temperature.
Evaporator pressure regulator (not supplied) is required.
Weight Ice production
Evaporator unit
160 lb (73 kg)
Condensing unit
Single-phase: 265 lb (102 kg)
3-phase: 320 lb (145 kg)
F
C
50
10
60
16
70
21
80
27
90
32
60
16
944
429
887
403
833
378
784
356
740
336
70
21
900
409
866
393
824
374
774
351
714
324
80
27
853
387
837
380
804
365
752
342
680
309
90
32
819
372
800
363
765
347
714
324
640
291
100
38
791
359
756
343
710
322
656
298
594
270
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
Inlet Water Temperature F/C
Ambient Air Temperature F/C
Air-cooled ice machine capacity/24 hrs.