Installation Instructions for Remote Condenser

4
REMOTE CONDENSING UNIT
1010/1410 single phase
1010 three phase
1410 three phase (Larkin)
Level unit
Securely attach base of unit using holes found in base plate
Required rack system capacity at 0 F (-18C) evaporator (EPR supplied by installer).
1010N: 7,700 Btu/hr (1940 kcal/hr)
1410N: 10,000 Btu/hr (2519 kcal/hr)
Condenser installation
2
Install condensing unit
2.1
Horizon Remote Single-Phase 208-230/60/1)
Min Circuit Ampacity Max Overcurrent Protection (MOP)
Horizon Remote Single Phase (208-230/60/1)
1010 10.7A 15A
1410 19.3A 30A
Horizon Remote 3 Phase (208-230/60/1)
1010 (Tecumseh) 9.94A 15A
1410 (Larkin) 15A 15A
Refer to wiring schematic located in condenser unit electrical box
CAUTION
Electrical disconnects required within
10' (3 m) for all hard wired connections
Install in accordance with NEC and local
electrical codes
Electrical requirements
2.2