Installation Instructions for Remote Condensing Unit

3
REMOTE CONDENSING UNIT
+20'
(+6.1 m)
+35'
(+10.7 m)
EVAPORATOR UNIT LEVEL
EVAPORATOR
UNIT
CONDENSER UNIT
maximum
line drop
CONDENSER UNIT
maximum
line rise
–15'
(–4.6 m)
75' max.
(22.8 m)
75' max.
(22.8 m)
PSIG
THE USA
MADE IN
OZ
PHASE
SINGLE
LOW SIDE
CHARGE
PART NO
RR
HZ
Easton Pennsylvania
208264
AMPS
AMPS
VOLTS
SERIAL NO
CORPORATION
MODEL
Service No.
Product
Module No.
REFRIGERANT
FULL LOAD AMPS
Stock Module Identification Plate
DESIGN PRESSURE HIGH SIDE
MAX. BRANCH CIRCUIT FUSE SIZE
MIN. BRANCH CIRCUIT AMPACITY
MOTOR COMPRESSOR THERMALLY PROTECTED
C
NSF
U
L
U
L
S-trap
required
P-trap
required
P-trap
required
Site layout:
Outdoor ambient temperature range: –20 F to 120 F (–29 C to 49 C)
Installation with condenser unit elevations above 20' (6.1 m) require an S-trap at the midpoint
of the rise and a P-trap at the top and bottom of the rise
Maximum line rise must not exceed 35' (10.7 m)
Maximum line set length must not exceed 75' (22.8 m)
Maximum line drop must not exceed 15' (4.6 m)
2.1
Condenser installation specications
1. 2