Installation Instructions for Remote Condensing Unit

4
REMOTE CONDENSING UNIT
Level unit
Securely attach base of unit using holes
found in base plate
Required rack system capacity at 0 F
(–18C) evaporator (EPR supplied by
installer).
1810N: 15,700 Btu/hr (3956 kcal/hr)
2110N: 18,200 Btu/hr (4586 kcal/hr)
Condenser installation
2
Install condensing unit
2.1
Condensing unit
1810
Single-Phase
1810
3-Phase
2110
Single-Phase
2110
3-Phase
Electrical 208-230V, 60Hz
Max Circuit HVACR breaker size 45A 25A 45A 30A
Min Circuit Ampacity 26.2A 15.7A 27.1A 19.9A
Refer to wiring schematic located in condenser unit electrical box
CAUTION
Electrical disconnects required within
10' (3 m) for all hard wired connections
Install in accordance with NEC and local
electrical codes
Electrical requirements