Installation Instructions for Remote Condensing Unit

8
REMOTE CONDENSING UNIT
CAUTION
The installer of the refrigeration line set must be USA Government Environmental Protection Agency (EPA)
certied in proper refrigeration handling and service procedures
A qualied person must perform all roof or wall penetration
Do not form unwanted traps in refrigeration lines. A service loop is not considered an oil trap.
Never coil excess refrigeration tubing
The compressor oil rapidly absorbs moisture. Minimize the exposure of the refrigeration system by not releasing
the condenser unit or evaporator unit holding charge until all line connections are nished and the system is
ready for evacuation.
WARNING
This unit contains an R404A holding charge
1. Make and connect line set run from the condensing unit to the evaporator unit with all
specications found in the installation specications section. DO NOT ATTACH QUICK
DISCONNECT CONNECTIONS TO THE EVAPORATOR! Do not overheat shut off valves on
the condenser unit or quick disconnects on evaporator unit.
Note: Insulate entire suction line (not the liquid line) including shut off valves to prevent
condensation.
7/8” suction
3/8” liquid
Refrigeration line installation
3
Refrigeration line installation: 7/8" suction / 3/8" liquid line (1810, 2110)
3.1
Braze supplied quick-connect lines onto
stub-ins
. DO NOT ATTACH QUICK
DISCONNECTS TO EVAPORATOR!
Braze the line set to the suction and
liquid lines. Run line set to the docking
station and stub in 2”.