Magnum Energy Integration Guide

505 Keystone Rd, Southampton, PA 18966
.
(877) 497 6937
.
sales@fortresspower.com
.
Fortresspower.com
Battery Bank Sizing with Magnum Equipment
Please make sure to go through these steps to make sure you have properly sized your system to
avoid damaging your battery. There are 4 ways of properly calculating the battery bank size for a
given system as outlined below:
1. Match Overcurrent Protection Device (Breaker Sizes)
   
  
2. Match Inverter Surge Rating to Maximum Current Rating of Battery
   
  
&
   
  
3. Match Charge Controller to Battery Bank charge capacity
  
 
4. Calculate the required battery bank capacity based on actual loads
  
(

)
   
(

)
𝑥 100% 80%
For the following battery bank size calculations, the below system assumptions apply:
1 Magnum MS4448PAE Inverter
o Recommended External DC Breaker Size: 175A DC
o Nameplate Capacity: 4300 Watts continuous / 90A DC
o Surge Capacity: 7500 Watts for 5 seconds / 156A DC
o Chargers
Capacity: 55A DC per Charger
2 parallel chargers: 110A DC
1. Match Overcurrent Protection Device (Breaker Sizes):
A Magnum MS4448PAE inverter requires externally obtained DC breaker.
Magnum recommends (1) 175A DC breaker
The LFP-5 has a 125A breaker
(
125𝐴 + 125𝐴
)
(
)
  
(
 
175𝐴)
The LFP-10 has a 150A breaker
(
150𝐴 + 150𝐴
)
(
)
  
(
 
175𝐴)
A single eVault 18.5 has a 250A breaker
(
250𝐴
)
(
)
  
(
 
175𝐴)