Morningstar Integration Guide
Load Current Compensation ……………………………… Default = 0.002 Ω (V/A), should be calculated
based on 0.35/C (Reduces Load LVD based on size of load with respect to battery Ah capacity)
Load HVD/High Voltage Disconnect/Reconnect............ Enable/14.30 V/13.80 V (May help to protect
loads from potentially harmful voltage spikes that can be caused by external charging sources continuing
to operate during battery removal)
Battery Charge LED Indications (Not intended for accurate SoC measurement):
LED G –> G/Y 75%+ = 13.30 V (3.325 V/per cell)
LED G/Y –> Y 50% - 74% = 13.0 V (3.25 V/per cell)
LED Y –> Y/R 25% - 49% = 12.8 V (3.2 V/per cell)
LED Y/R –> R 10% or below = 12.5 V (3.125 V/per cell)
(More information regarding these settings provided by Morningstar
)
These settings are available for the Morningstar controllers listed below:
48V systems:
TriStar MPPT (compatible with 12V, 24V, 36V, 48V, 60V nominal systems)
TriStar MPPT 600V (compatible with 24V, 36V, 48V and 60V nominal systems)
TriStar [PWM] (compatible with 12V, 24V, 36V and 48V nominal systems)
Communications hardware required for programming Custom Settings with MSView:
TriStar, TriStar MPPT, TS-MPPT-600V
Includes an RS-232 port for connection to a PC.
EMC-1 Ethernet MeterBus Converter-
http://www.morningstarcorp.com/products/ethernet-meterbus-converter/
Tripp Lite U209-000-R USB / Serial DB-9 (RS-232) Adapter Cable (not available from Morningstar)
All TS-MPPT-60 (150V and 600V) models also include an Ethernet port and EIA-485 port.
MSView Software Download: http://www.morningstarcorp.com/msview/
MSView Configuration Files:
https://www.morningstarcorp.com/wp-content/uploads/2019/04/Fortress-Power-MSView-Configuratio
n-Files.zip
Other links:
Copyright 2018 Morningstar Corporation / All rights reserved Page 3