Magnum Energy Integration Guide
505 Keystone Rd, Southampton, PA 18966
.
(877) 497 6937
.
sales@fortresspower.com
.
Fortresspower.com
Setting up a Fortress Power Lithium Battery using Magnum Inverter/Charger
Magnum MS4448PAE Inverter Battery Turn On/Off Levels Setting
80% DoD, 6000
cycles
90% DoD, 3000
cycles
Low Battery Cut In
Voltage
51
.5
V
51
V
Low Battery Cut Out
Voltage (1 Minute Delay)
48.8V
48.8V
LBCO Voltage (No
Delay)
48V
High Battery Cut
Out
Voltage
LFP-10 & LFP-15: 63
V
eVault: 61 V
High Battery Cut In
Voltage
LFP-10 & LFP-15:
61.8V
eVault:
59.8 V
Low Battery - The inverter will shut off whenever the battery voltage falls to the LBCO
(Low Battery Cut Out) level to protect the batteries from being over-discharged. After the
inverter has reached the LBCO level and turned off, the inverter will automatically restart
after one of the following conditions:
o AC Power is applied and the inverter begins operating as a battery charger.
o Battery voltage rises to the LBCI (Low Battery Cut In) level.
High Battery - In the event the battery voltage approaches the HBCO (High Battery Cut
Out) level, the inverter will automatically shut down to prevent the inverter from supplying
unregulated AC output voltage. The inverter’s status LED turns off when a high battery
fault condition occurs. The inverter will automatically restart when the battery falls to the
HBCI (High Battery Cut In) level.
*High battery voltage may be caused by excessive or unregulated voltage from the solar panels
or other external charging sources
Magnum MS4448PAE Inverter/Charger Values
80% DoD, 6000
cycles
90% DoD, 3000
cycles
Shore Max
51.5V
51V
01 Search Watts
48.8V
48.8V
02 LowBattCuutOut
48V
03 Batt AmpHrs
LFP-10 & LFP-15: 63
V
eVault: 61 V
04 Battery Type
LFP-10 & LFP-15:
61.8V
eVault: 59.8 V
05 Charge Rate **
100%