7.4 Parameter set up guide in Charger/Inverter
Before commissioning the energy storage system, the appropriate controller and inverter settings must
be programmed per the manufacturer’s recommendations. Consult the manufacturer’s manuals and/or
access technical support (Darfon, Schneider, Outback, SMA, Sol-Ark, Magnum, Outback).
Although Fortress Lithium batteries can perform at very high rates and depths of discharge within a
very wide temperature range, in order to achieve extended life cycles and to comply with the Warranty,
the following guidelines should be followed:
Understand Charge Stage
1) Bulk Charge: Charge at Constant Current
(CC) to Bulk/Absorb Voltage
2) Absorption Charge: Maintain Constant
Bulk/Absorb Voltage (CV)
3) Terminate when charge current drops
below 0.05C
4) Unlike Lead Acid batteries, Lithium Ferro
Phosphate batteries do not require Float
Charge
The Battery Parameter Setting Guides with Schneider and Outback Inverters/Chargers are available to
download on www.fortresspower.com/Resource
Recommended operating parameters of charger/Inverters For 3,000 Cycles:
Operating temperature range: 35 F to 120 F (2 °C to 49°C)
Recommended operating parameters of charger/Inverters For 6,000 Cycles:
Operating temperature range: 35 F to 110 F (2°C to 43°C)
Storage must be equal to or more than twice the rated output of the Inverter
At the End of Cycle Life capacity is Equivalent to 70% Retained Capacity
CAUTION! Do Not Operate Fortress Lithium Batteries at an average temperature
exceeding 30 °C / 86 F over the life of the battery.