Schneider Electric Integration Guide
Rev 2.2 02-10-22
Fortress Power – Schneider XW Pro Inverter Guide
505 Keystone Rd, Southampton, PA 18966 . (877) 497 6937. sales@fortresspower.com . Fortresspower.com
16
2. Open Loop Settings
***All Open Loop Settings are programmable with a SCP, Insight Local or/and Insight Cloud. Disregard the
communication cable that would go from battery to inverter. Use these settings for XW + Inverter
Settings for Fortress Batteries with Schneider Inverters
Charger Setting > Custom Setting
80% DoD, 6000 cycles
Battery Type
Custom
Charge Cycle
2StgNoFloat
Bulk Voltage
54.4 V
Max Bulk Current
eFlex:55A per battery
eVault:100A per battery
eVault MAX 150 per battery
LFP-10: 70A per battery
Max Discharge Current
eFlex: 60A per battery
eVault: 160A per battery eVault MAX:
LFP-10: 100A per battery
Battery Capacity
eFlex: 105AH per battery
eVault: 360AH per battery
eVault MAX: 360AH per battery
LFP-10: 200AH per battery
Max Charge Rate Percentage (%)
eFlex:55A per battery
eVault:100A per battery
eVault MAX 150 per battery
LFP-10: 70A per battery
Divided by Total Inverter DC Amperage
Default Battery Temperature
Warm
Recharge Volts
51.3
Grid Support Volts**
53
Absorb Volts
54.4
Absorb Time
1 Hour
Charge Block Start
Default
Charge Block Stop
Default
Advanced Settings > Inverter Settings
Low Battery Cut Out Voltage
48V (50V if allowed)
LBCO Hysteresis
2.0V
LBCO Delay
5 Sec
High Battery Cut Out Voltage
61V (58V if allowed)
Search Watts
Default
Search Delay
Default