Schneider Electric Integration Guide
Rev 2.2 02-10-22
Fortress Power – Schneider XW Pro Inverter Guide
505 Keystone Rd, Southampton, PA 18966 . (877) 497 6937. sales@fortresspower.com . Fortresspower.com
17
Settings with Schneider Charge Controllers
***Parameter Setting for Fortress Batteries with Schneider XW+ & XW Pro MPPT 60/80
Advanced Setting > Charger Setting
Battery Type
Custom
Custom Setting
80% DoD, 6000 cycles
Charge Mode
3 Stage
Eqlz Support
Disabled
Bulk Voltage
54.4 V
Absorb Voltage
54.4 V
Absorb Time
60 minutes
Float Voltage
54.4 V
Battery Temperature Compensation
0mV/C
Battery Capacity
eFlex: 105AH per battery
eVault: 360AH per battery
eVault MAX: 360AH per battery
LFP-10: 200AH per battery
Max Charge Rate Percentage*
eFlex:55A per battery
eVault:100A per battery
eVault MAX: 150A per battery
LFP-10: 70A per battery
Divide by total CC amp output
Charge Cycle
Warm
Recharge Volts
53 V
Absorb Time
1 Hour
Default Battery Temperature
Warm
Battery Voltage (Auto-detected)
48V
Note: The charge controllers can be set to a 3-stage charging cycle, but the inverter should be kept in a 2
stage charging cycle. Doing so, as well as setting the charge controller recharge voltage to be greater than
that of the inverter recharge voltage, will prioritize charge controller charging over the inverter charging.
Inverter charging is a grid/generator charge which has a lower priority than solar charge controller charging.
3. Additional Options
Generator Settings (Applicable to all Mode Settings)
20% state of charge is approximately 51.0V.
95% charge is approximately 53.7V. A 100% charge 54.4V.
NOTE: Voltages are open circuit resting measurement. The settings that would discharge the battery down
to 49V, is too low for Fortress batteries. Fortress batteries should only be intentionally discharged down to
20% SoC or 51.4V and then be recharged by available charging sources.