Table of contents 1. Introduction 1-1. Transportation 1-2. Preliminary Steps 1-3. Initial Setup 1-4. Important Safety Instructions 1-5. Maintenance, Service and Faults 2. Operation 2.1 Unpacking and inspection 2.2 UPS front and rear panel views 2.3 Installation Procedure 2.4 Forza Tracker monitoring software 3. Advanced operation 3.1 Description of buttons and functions 3.2 LCD Panel 3.3 Audible alarm 3.4 Abreviations on the LCD display 3.5 UPS parameter settings 3.6 Operating mode description 3.
1. Introduction Thank you for purchasing the Forza Atlas 3000 Online UPS. To enjoy all the features and benefits of this unit, please read and follow all installation and operation instructions thoroughly before unpacking, installing or operating this device. After you have read this manual, keep it in a safe place for future reference.
1-5. Maintenance, service and faults • The voltage used by this UPS may be hazardous. The unit contains no user serviceable parts; do not attempt to disassemble the unit. Only qualified service technicians can perform maintenance on the unit. Failure to adhere to this could cause personal injury or equipment malfunction and void the warranty. • Caution - risk of electric shock.
Rear panel view 1. Programmable outlets: connect to non-critical loads. 2. Output receptacles: connect to high critical loads. 3. AC input 4. Input circuit breaker 5. Network/Fax/Modem surge protection 6. Emergency power off (EPO) connector 7. USB communication port 8. RS-232 communication port 9. SNMP intelligent slot 10. Output terminal 11. Output circuit breaker 12. Input terminal 2.3.
Step 3: Communication connection Communication port: USB port RS-232 port Intelligent slot To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the USB/RS-232 port, and the other end to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC. The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card.
Installation procedure for Windows users: 1. Use the supplied CD or go to the website: http://www.forzaups.com. 2. After clicking the software icon, choose the required operation system. 3. Follow the on-screen instructions to install the software. 4. When you finished downloading all required files, enter the serial No (installation password): 5242-87f6-64re-di8d-986u to install the software (include the hyphens). 5. In order to access as Administrator, input the password: 111296. 6.
3-2.
Display Function Backup time information Indicates the remaining backup time in pie chart. Indicates the remaining backup time in numbers. H: hour, M: minute, S: second Fault information Indicates that the warning and fault occurs Warning and fault code indicators. The meaning of the codes is listed in the section below. Mute operation Indicates that the UPS alarm is disabled. Output & battery voltage information Output voltage, frequency or battery voltage.
3-3. Audible alarm Battery mode Beeps once every 4 seconds Low battery Beeps once every second Overload Beeps twice every second Fault Beeps continuously Bypass mode Beeps every 10 seconds 3-4. Abbreviations on the LCD display Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High line transfer LLS Low line transfer BAT Battery CF Converter EP EPO TP Temperature CH Charger 3-5.
01: Output voltage settings Interface Setting Parameter 3: Output voltage For 200/208/220/230/240 VAC, you may choose any of the following output voltages in parameter 3: 200: The output voltage is 200VAC 208: The output voltage is 208VAC 220: The output voltage is 220VAC 230: The output voltage is 230VAC 240: The output voltage is 240VAC For 100/110/150/120/127 VAC, you may choose any of the following output voltages : 100: The output voltage is 100VAC 110: The output voltage is 110VAC 115: The output vol
05: ECO voltage range settings Interface Setting Parameter 2 & 3: Press the UP or Down key to choose the acceptable high and low voltage values for the ECO mode. HLS: High line transfer in ECO mode as set in parameter 2. For 200/208/220/230/240 VAC, the setting in parameter 3 ranges between +7V and +24V of the nominal voltage. For 100/110/115/120/127 VAC, the setting in parameter 3 ranges between+3V and +12V of the nominal voltage. LLS: Low line transfer in ECO mode as set in parameter 2.
08: Enable/Disable programmable outlets Interface Setting Parameter 3: Activates or cancels the programmable outlet feature. ENA: Programmable outlets enabled DIS: Programmable outlets disabled 09: Backup time setting for programmable outlets Interface Setting Parameter 3: Sets the backup time limits for the programmable outlets. 0-999: Use this setting to define the programmable outlets backup time in minutes, from 0-999, in order to connect non-critical devices on battery mode.
3-6. Operation mode description Operating mode Description Online mode When the input voltage is within acceptable range, the UPS will supply pure and stable AC power to connected loads. The UPS will also charge the battery in online mode. ECO mode Energy saving mode: When the input voltage is within the voltage regulation range, the UPS will bypass voltage to loads for energy saving.
3-8.
4. Troubleshooting guide If the UPS system does not operate correctly, use the table below to troubleshoot the problem. Symptom Even though the mains supply is normal, there are no status indicators or alarms. Possible cause Remedy The AC input cable is not properly connected. Check to make sure the power cord is firmly connected to a AC wall socket The AC input is connected Plug the power cord to a wall socket. to the UPS outlet.
Symptom Possible cause Remedy Fault code 14 becomes illuminated along with the icon on the LCD display, and the alarm starts beeping continuously. The UPS shuts down automatically upon detecting the overload condition in the output. Check the output wiring and if connected devices are short-circuited. Fault code 1, 2, 3, 4, 11, 12, 13 and 41 become illuminated on the LCD display, and alarm starts beeping continuously. A UPS internal fault has occurred. There are two possible causes: 1.
6. Specifications Model FDC-003K 3000 VA / 2400 W CAPACITY* INPUT Low line transfer Voltage range Low line comeback High line transfer High line comeback Frequency range Phase Power factor OUTPUT Output voltage AC voltage regulation Frequency range (synchronized range) Frequency range (batt.