Specifications

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient
temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer or
service center.
Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:
Fault code 14 becomes illuminated
along with the icon on the
LCD display, and the alarm starts
beeping continuously.
Fault code 1, 2, 3, 4, 11, 12, 13
and 41 become illuminated on
the LCD display, and alarm starts
beeping continuously.
Battery backup time is shorter
than its nominal value.
The UPS shuts down
automatically upon
detecting the overload
condition in the output.
Defective batteries.
Batteries are not fully
charged.
Charge the batteries for at least
5 hours and then check their
capacity. If the problem persists,
consult your dealer.
Contact your dealer for
a replacement.
A UPS internal fault has
occurred. There are two
possible causes:
1. Power is continued to
be supplied to the load,
but is done directly from
the AC grid via a bypass.
2. Power is no longer
supplied to the load.
Check the output wiring and
if connected devices are
short-circuited.
Please contact the dealer or
service center.
Symptom Possible cause Remedy
5. Storage and maintenance
Storage
Batteries must not be discarded as regular household waste! As part of the
company’s eco-friendly approach, we encourage you to follow all applicable local
waste regulations to dispose of your used devices and batteries properly.
Storage temperature Recharge frequency Runtime
-25°C - 40°C
40°C - 45°C
Every 3 months
Every 2 months
1-2 hours
1-2 hours