Installation Manual

© 2015 Sensata Technologies
Page 19
Installation
2.3.3 Recommended Ground Fault Circuit Interruption (GFCI) Breakers
Some electrical safety codes require the use of GFCI’s. In compliance with UL standards, the
following GFCI’s have been tested and have been found to function properly when connected to
the inverter’s AC output (there are others on the market that will work as well):
• Shock Sentry
TM
#VGF15W Leviton Smart Lock #8899-A Hubbel #GF520EMBKA
WARNING: Risk of electric shock. Use only ground-fault circuit interrupters [receptacle(s)
or circuit breaker(s)] that are compatible with your MS-PAE inverter. Some types may
fail to operate properly when connected to this inverter equipment.
2.3.4 AC Input and Output Wiring Connections
The MS-PAE Series inverter/charger has a six-connection AC terminal block and two AC ground
terminals that are used to connect the inverter’s AC input/output wiring. To access the AC terminal
block and the ground terminals, remove the two Phillips screws that hold the AC access cover
plate to the left side of the inverter (see Figure 1-3, Item 15).
Each connection on the AC terminal block is rated for 221°F (105°C) and can accept a #18 to #4
AWG (0.82 to 21.1 mm
2
) CU solid/stranded wire. Each connection uses a set screw with slot-head,
and the recommended tightening torque is 16 in lbf (1.8 Nm).
Each AC ground terminal can accept one #14 to #6 AWG (2.1 to 13.3 mm
2
) stranded wire.
Recommended tightening torque is 45 in lbf (5.1 Nm).
Info: The two neutral terminals are common to each other and can be used in any
combination or order. In a residential application, it is often easier to connect only one
AC neutral wire to the inverter and make the other neutral connections at a central
point, such as in the AC electrical panel.
Figure 2-8, AC Terminal Block
AC HOT 1 IN
AC HOT 2 IN
AC HOT 1 OUT
AC HOT 2 OUT
AC NEUTRAL
AC NEUTRAL
AC GROUNDS
(
X2)