Installation Manual
www.fullriverbattery.com Page 19
Appendix
A.1 - TEMPERATURE RANGES
A.2 - STATE OF CHARGE (S.O.C) VS. OPEN CIRCUIT VOLTAGE (O.C.V.)
Storage
Operation
ChargewithTC
Chargew/oTC
5°F to 122°F (-15°C to 50°C)
5°F to 104°F (-15°C to 40°C)
5°F to 122°F (-15°C to 50°C)
32°F to 104°F (0°C to 40°C)
Condition Recommended
-40°F to 160°F (-40°C to 71°C)
-40°F to 160°F (-40°C to 71°C)
-40°F to 160°F (-40°C to 71°C)
5°F to 122°F (-15°C to 50°C)
Maximum
2.14
2.12
2.10
2.08
2.06
2.03
2.01
1.99
1.96
1.94
2V
100
90
80
70
60
50
40
30
20
10
State of Charge
(S.O.C.)
Open Circuit Voltage (O.C.V.)
6.42
6.36
6.30
6.24
6.17
6.10
6.03
5.96
5.88
5.81
6V
8.56
8.48
8.40
8.32
8.23
8.14
8.04
7.94
7.84
7.74
8V
12.83
12.72
12.60
12.47
12.34
12.20
12.06
11.91
11.76
11.61
12V
At 80°F (27°C)