Manual

www.franklinfueling.com
PN & Rev: 0000210C
E-mail: tech@franklinfueling.com FAX 1-207-282-9002 TEL 1-800-984-6266 PAGE 1 of 2
sales@franklinfueling.com FAX 1-207-283-0158 TEL 1-800-872-3455
REPLACEMENT
PART
INSTRUCTIONS
Memory Backup Battery Replacement Instructions
for Tank Sentinel, AutoStik, & BulkStik ATGs
Parts & Materials
Required:
One new 3 volt lithium
battery (INCON P/N:
TSSP-BAT / 390-0004), a
thin piece of adhesive tape,
and a digital multimeter with
test probes.
Diagram:
Testing the
Battery ( B1 )
Use a digital multimeter set
to read 5 DC volts and
measure the DC voltage
between the + battery
terminal and ground or
the yellow-colored metal
shield
(+2.8 to +3.3 volts DC is good).
When to Test the
Battery Voltage (Schedule): Yearly after the first two years of operation or use.
DANGER Electrical Shock Hazard. Make sure all safety shields are installed to
prevent electrical shocks — DO NOT touch any device other than the battery.
Removal & Installation Steps ( with Tank Gauge Power ON & SW 1 ON ):
1.) Printout the complete system and tank setup reports for all tanks. ( Note – if the
power goes out or is turned off while the battery is out of its holder then all of the
setup/programmed values of the system will be lost. If this happens then the entire
tank gauge will have to be reprogrammed ).
WEDGE UP HERE
ABOUT 1/8 INCH
Battery Cutaway
Side View
b
PRY OUT HERE
a
Yellow
colored
metal
shield
b
TS-1001/N-N U10
VER No. DATE
a
Replace the battery if the voltage reading is below
2.8 volts DC