Operators Guide Manual

31
FMS
Probe Alarms
Displayed Alarm Description Recommended Actions Reference Source
Float Height
Error
A oat on the probe listed with the alarm is 
being monitored at a varying height outside 
of thresholds. Causes can include broken 
oat and programming, or mistakenly 
associating a gasoline and diesel oat.
Verify Probe programming. Visually 
inspect that the probe oat type matches 
the type of product. Inspect magnet and 
probe shaft for cracks or debris and 
clean if necessary.
Probes Setup in
Programming Manual**) 
/ Applicable Equipment 
Guide*
Float Missing A oat on the probe listed with the alarm 
has not been detected or the probe was 
programmed with the incorrect number of 
oats.
Verify the ‘number of oats’ in Probe 
programming. Number of oats must 
match number of oats installed. Float 
must be lower than 5" from the bottom of 
the probe head.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
High Water
Level
The water oat on the Tank/Manifold listed 
with the alarm is above the programmed 
High Water Level Limit.
Verify that the programmed limit is 
correct. Verify that the Water Level 
values on the console correspond with 
the actual water level in the tank.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
High Product
Level
The product oat on the Tank/Manifold listed 
with the alarm is above the programmed 
High Product Level Limit. Tank may be close 
to an overfull condition.
Verify that the programmed limit is 
correct. Verify that the Gross Product 
Level values on the console correspond 
with actual product level in the tank.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
High High
Product Level
The product oat on the Tank/Manifold listed 
with the alarm is above the programmed 
High High Product Level Limit. Tank may be 
near an overfull condition.
Verify that the programmed limit is 
correct. Verify that the Gross Product 
Level values on the console correspond 
with actual product level in the tank.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Low Product
Level
The product oat on the Tank/Manifold listed 
with the alarm is above the programmed 
Low Product Level Limit. Tank may be close 
to an empty condition.
Verify that the programmed limit is 
correct. Verify that the Gross Product 
Level values on the console correspond 
with actual product level in the tank.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Low Low
Product Level
The product oat on the Tank/Manifold listed 
with the alarm is above the programmed 
Low Low Product Level Limit. Tank may be 
near an empty condition.
Verify that the programmed limit is 
correct. Verify that the Gross Product 
Level values on the console correspond 
with actual product level in the tank.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
No Probe
Detected
This alarm indicates a communication error 
between the console and the probe listed 
with the alarm.
Verify Probe programming. Inspect the 
probe wiring from the probe module to 
the probe. 
Probes Setup in
Programming Manual** / 
Installation Guide**
Probe
Synchronization
Error
This alarm indicates a communication error 
between the console and the probe listed 
with the alarm.
Verify Probe programming. Inspect the 
probe wiring from the probe module to 
the probe. 
Probes Setup in
Programming Manual** / 
Installation Guide**
RTD Table Error The RTD Table programmed for the probe 
listed with the alarm is incorrect.
Verify the RTD Table programming. Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Temperature
Error
This alarm indicates a temperature sensor 
error or failure inside the probe shaft of the 
probe listed with the alarm.
Verify the RTD Table programming. 
Visually inspect probe shaft for defects 
and cracks.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Unstable Probe This alarm indicates inconsistent data from 
the probe listed with the alarm.
Inspect the probe wiring from the probe 
module to the probe. Verify that the 
product in the tank is both physically and 
thermally stable.
Installation Guide** / 
Applicable Equipment 
Guide*