Operators Guide User guide

28
System
Displayed Warning Description Recommended Actions Reference Source
IS Barrier Violation The system has received an indication 
that there is a Non-Intrinsically Safe 
module installed in the IS area or that 
the IS barrier has been removed.
Visually verify that all modules are 
installed on the correct side of the IS 
Barrier.
Installation Guide / 
Applicable Bulletins*
Low Battery Backup Battery should be replaced. Replace the backup battery with an exact 
replacement from FFS.
Installation Guide / 
Applicable Bulletins*
Modem Error The number of expected Modem 
Modules does not equal the number of 
Modem Modules installed.
Verify the physical number of Modem 
Modules installed and compare with the 
number listed under Conguration >  
Modem Setting.
General Setup in
Programming Manual
 / Applicable Bulletins*
Power Supply Module
is Ofine
This warning is only possible if there 
is a TS-EXPC expansion console 
connected. Failure to recognize the 
expansion console’s PSM.
Cycle power to the console. Visually verify 
that the green ‘RUN’ light on the module 
is on continuously after the system boot is 
complete.
Installation Guide / 
Applicable Bulletins*
Printer Paper Jam
(Impact Printer Only)
Paper feed error. Paper or debris is 
stuck in the printer.
Visually inspect the printer for the 
problem. Correctly route the paper through 
the printer to clear this warning.
Installation Guide / 
Applicable Bulletins*
Check Printer
(Thermal Printer Only)
Printer is out of paper, or the printer 
door is open.
Make sure the printer has paper, and the 
printer door is closed completely.
Installation Guide** / 
Applicable Bulletins*
Printer Motor
Temperature or Printer
Head Temperature
(Thermal Printer Only)
Printer motor or print head high 
temperature persists for 2 minutes. 
This can be caused by printing long 
reports and can be aggravated 
by having the printer in a hot 
environment. If the motor remains hot, 
it could eventually cause the board 
to fail: the temperature alarms would 
go away and be replaced by a printer 
module mismatch alarm.
If less than 2 minutes, printer will resume 
printing after a short cool-down period.  
Keep the console area cool and ventilated. 
If the printer should remain too hot and 
generate a printer module mismatch 
alarm, the printer will most likely need 
replacing.
Installation Guide** / 
Applicable Bulletins*
Probe Module
is Ofine
The specied Probe Module listed with 
the alarm has experienced a problem 
or may not be recognized by the 
Controller Module.
Cycle power to the console. Visually 
verify that the green ‘RUN’ light on 
the applicable Probe Module is on 
continuously after the system boot is 
complete.
Installation Guide / 
Applicable Bulletins*
Probe Module
Number Mismatch
The number of expected Probe 
Modules does not equal the number of 
Probe Modules installed.
Verify the physical number of Probe 
Modules installed and compare with the 
number of Probe ‘Modules Expected’ in 
the programming.
General Setup in
Programming Manual
 / Applicable Bulletins*
Relay Module
Number Mismatch
The number of expected Relay 
Modules does not equal the number of 
Relay Modules installed. 
Cycle power to the console. Visually 
verify that the green ‘RUN’ light on 
the applicable Relay Module is on 
continuously after the system boot is 
complete.
Installation Guide / 
Applicable Bulletins*
Relay Module
is Ofine
The specied Relay Module listed with 
the alarm has experienced a problem 
or may not be recognized by the 
Controller Module.
Verify the physical number of Relay 
Modules installed and compare with the 
number of Relay ‘Modules Expected’ in 
the programming.
General Setup in
Programming Manual
 / Applicable Bulletins*
Relay Module
Setup Error
This alarm is an indication that all 
channels have been enabled. With all 
six (6) 2A relay channels in use, 10A
channels seven (7) and eight (8) may 
not be enabled. 
Verify Relay Module programming. Module Setup in
Programming Manual
* Bulletins and the T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on 
Franklin Fueling’s web site - http://www.franklinfueling.com/service/.   Select Technical Documentation / Fuel Management Systems.