Change the Baud Rate
Important!: Unrecognizable characters appear on the screen after placing the radio into Setup mode.
l Unrecognizable characters usually indicate a Baud Rate problem.
l The problem may also be that the radio under test is a TTL version or has been set to
RS485 and not RS232. If the radio is TTL or in RS485 mode, verify connection through the
Diagnostic port. Gibberish before the Setup button is pressed indicates Diagnostics is
enabled in a Master.
1.
Click .
2. On the File menu, click Properties.
3. Click Configure.
4. Change these settings and click OK:
l Baud Rate to 19200
l Data Bits to 8
l Parity to None
l Stop Bits to 1
l Flow Control to 1
5. Click OK to close the Properties dialog box.
6.
Click .
7. Return the radio to Setup mode.
The Setup menu screen appears.