3.2.2. Point-to-MultiPoint Network Quick Start (Terminal Interface)
1. Connect the radio to the serial port of a computer using either a serial cable or the
diagnostics cable.
2. Connect the radio to a power source.
Important!: Power supply ranges and recommendations vary depending on model.
Verify the specifications for the model prior to connecting power.
3. Open a terminal emulator session.
Use the Tool Suite Setup Terminal application if a terminal emulator is not available.
4. Connect to COMx (where 'x' is the number of the COM connected port).
5. Set these options:
l Data Rate: 19,200
l Data Bits: 8
l Parity: None
l Stop Bits: 1
l Flow Control: None
6. Press the Setup button on the radio.
If using the diagnostics cable, press <Shift+U>.
l The three LEDs on the radio should all turn green , indicating Setup mode.
l The Main menu appears on the screen.
7. Press <0> to access the Operation Mode menu.
8. Press <2> to set the radio as a Point-to-MultiPoint Master or
Press <3> to set the radio as a Point-to-MultiPoint Slave.
9. Press <Esc> to return to the Main menu.
Note: A MultiPoint network can have only one Master, unless running in Multi-Master Sync
mode.
For more information, see Multi-Master Sync (on page 106).
10. Press <1> on the Main menu.
11. Change the Baud Rate, Data Parity, and Modbus RTU to match the device that the
radio is to be attached to.
12. Press <Esc> to return to the Main menu.
13. Press <3> in the Main menu.
14. Set these parameters so they are the same on all radios in the network:
l FreqKey
l Max Packet Size
l Min Packet Size
l RF Data Rate