Service and Parts Manual (2019, 2020, 2021, 2022)

Table Of Contents
12 PB
SPECIFICATIONS
Capacities and Selection Data
Floating Air Pro / Premier Cooling Extended Capacity (By System Model)
System Model
Outdoor Air
Temp. (°F DB)
Indoor Air Temp. °F DB / °F WB
80 /67
TC SHC PI
kBtu/h kW
FPHW091/A
32 9.56 6.69 0.26
41 10.09 7.06 0.36
50 10.35 7.24 0.47
59 10.96 7.67 0.50
67 11.18 7.83 0.59
77 11.57 8.10 0.70
82 11.90 8.33 0.81
87 11.78 8.25 1.00
95 11.63 8.14 1.02
104 11.08 7.76 1.02
115 9.94 6.96 1.00
FPHW121/A
32 10.76 7.53 0.27
41 11.29 7.90 0.36
50 11.93 8.35 0.42
59 12.17 8.52 0.59
67 12.44 8.71 0.78
77 12.68 8.88 1.01
82 13.25 9.28 1.07
87 12.98 9.08 1.16
95 12.55 8.79 1.25
104 11.90 8.33 1.24
115 10.53 7.37 1.18
FPHW093/A
32 8.54 5.97 0.26
41 8.72 6.10 0.36
50 9.15 6.41 0.47
59 9.53 6.67 0.60
67 9.89 6.92 0.69
77 10.21 7.14 0.80
82 10.37 7.25 0.90
87 10.28 7.19 0.91
95 10.11 7.08 0.92
104 9.85 6.89 0.89
115 9.26 6.48 0.88