Service and Parts Manual (2019, 2020, 2021, 2022)

Table Of Contents
13 PB
SPECIFICATIONS
Capacities and Selection Data
Floating Air Pro / Premier Cooling Extended Capacity (By System Model)
System Model
Outdoor Air
Temp. (°F DB)
Indoor Air Temp. °F DB / °F WB
80 /67
TC SHC PI
kBtu/h kW
FPHW123/A
32 10.66 7.46 0.35
41 11.39 7.97 0.54
50 12.09 8.46 0.65
59 12.73 8.91 0.76
67 13.13 9.19 0.86
77 13.62 9.54 0.95
82 14.07 9.85 1.09
87 13.85 9.69 1.15
95 13.25 9.27 1.22
104 12.15 8.50 1.19
115 9.81 6.87 1.10
FPHW183/A
32 16.78 11.75 0.97
41 17.75 12.43 1.09
50 18.40 12.88 1.22
59 18.62 13.03 1.30
67 19.03 13.32 1.35
77 19.31 13.52 1.41
82 19.55 13.69 1.60
87 19.26 13.48 1.91
95 18.57 13.00 1.91
104 17.27 12.09 2.11
115 15.80 11.06 2.11
FPHW243/A
32 22.14 15.50 1.09
41 25.05 17.54 1.47
50 26.49 18.55 1.72
59 27.28 19.10 1.93
67 27.51 19.26 2.13
77 27.72 19.40 2.35
82 28.08 19.66 2.52
87 27.35 19.15 2.72
95 26.47 18.53 3.02
104 22.76 15.93 2.89
115 18.34 12.84 2.60