Service and Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- SPECIFICATIONS
- INSTALLATION
- MAINTENANCE
- R-410A SEALED SYSTEM REPAIR
- TROUBLESHOOTING
- Diagnostic Codes
- Outdoor Unit
- Outdoor Unit When The Compressor Is In Operation
- Indoor Unit
- Led Display
- Test the jumper terminals
- Protection Circuit Fault Isolation
- Compressor Fault Isolation
- Electric FIlter Board Fault Isolation
- Electrical Communication Fault ISOLATION
- Unit does not run
- Error Code 39-DC FAN
- Error Code 39-PG Fan
- Error Code 9
- Error Code 13
- Error Code 8
- Error Code 15
- Error Code 16 Cooling Mode
- Error Code 16 Heating Mode
- Error Code 21 Cooling Mode
- Error Code 11 EEPROM Fault
- Error Code 20
- Error Code 33
- Error Code 34
- Error Code 14
- Error Code 1
- Error Code 2
- Error Code 6
- COMPONENTS TESTING
- WIRING DIAGRAMS
- PARTS CATALOG
- Introduction
- 115V Indoor Unit 9-12K
- 230V Indoor Unit 9-12K
- 230V Indoor Unit High Seer 9K
- 230V Indoor Unit High Seer12K
- 230V Indoor Unit 18K
- 230V Indoor Unit 24K
- 230V Indoor Unit 36k
- 115V Outdoor Unit 9K
- 115V Outdoor Unit 12K
- 230V Outdoor Unit 9k
- 230V Outdoor Unit 12k
- 230V Outdoor Unit 18k
- 230V Outdoor Unit 18k
- 230V Outdoor Unit 24k
- Outdoor Unit 36k
- 230v Outdoor Unit 9K HIGH SEER
- 230V Outdoor Unit 12K HIGH SEER
- APPENDIX
- LIMITED WARRANTY
- CUSTOMER SATISFACTION and QUALITY ASSURANCE
- FRIEDRICH AUTHORIZED PARTS DEPOTS
23 PB
OPERATION
Fan Only Mode Operation
During the appliance run in this mode; the compressor and outdoor fan stop and the indoor fan operates under the pre-
setting of air volume. The louver swing and the indoor fan speed is the same as the Heating Mode.
Defrost
Conditions for Defrost Activation:
The following three conditions must be met to activate Defrost.
• Condition 1: Outdoor ambient sensor is below 28.4F
• Condition 2: When the heating compressor consecutively runs for 40 minutes .
• Condition 3: The difference between the condenser coil pipe sensor outdoor ambient temperature sensor ≥10F.
Defrosting actions:
• The compressor stops, and the outdoor fan stops after delay of 30 seconds; in 50 seconds the four-way valve is powered
off; and in 10 seconds the compressor starts and runs at “defrosting frequency”.
Conditions for ending defrosting:
Defrosting is over if either of the conditions below are met.
• Condition 1: The accumulated time of defrosting is longer than 12 minutes (EEPROM setting value in the current
operating mode).
• Condition 2: If the temperature of coiled pipe is equal to or higher than 57°F (EEPROM setting value in the current
operating mode).
Actions of exiting the defrosting state:
• The compressor stops. 50 seconds later the four-way valve opens, and another 10 seconds later the compressor and
outdoor fan restart and begin normal operation.
Conditions of anti-freezing prohibition of frequency rising:
• Condition 1: in the case of anti-freezing frequency decreasing, the temperature of indoor heat exchanger rises to “anti-
freezing frequency decreasing temperature”.
• Condition 2: in normal operation, the temperature of indoor heat exchanger reaches “anti-freezing prohibition of
frequency rising temperature”.
• If either of the above two conditions is met, the product will enter anti-freezing prohibition of frequency rising state.
• Anti-freezing prohibition of frequency rising operation: the compressor is kept at the current frequency, which may
decrease according to situations while cannot rise. The outdoor fan runs.
Condition for the end of anti-freezing prohibition of frequency rising state:
• When the temperature of indoor heat exchanger rises to “anti-freezing releasing temperature”, the state of anti-
freezing prohibition of frequency rising is released.