Service and Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- SPECIFICATIONS
- INSTALLATION
- MAINTENANCE
- R-410A SEALED SYSTEM REPAIR
- TROUBLESHOOTING
- Diagnostic Codes
- Outdoor Unit
- Outdoor Unit When The Compressor Is In Operation
- Indoor Unit
- Led Display
- Test the jumper terminals
- Protection Circuit Fault Isolation
- Compressor Fault Isolation
- Electric FIlter Board Fault Isolation
- Electrical Communication Fault ISOLATION
- Unit does not run
- Error Code 39-DC FAN
- Error Code 39-PG Fan
- Error Code 9
- Error Code 13
- Error Code 8
- Error Code 15
- Error Code 16 Cooling Mode
- Error Code 16 Heating Mode
- Error Code 21 Cooling Mode
- Error Code 11 EEPROM Fault
- Error Code 20
- Error Code 33
- Error Code 34
- Error Code 14
- Error Code 1
- Error Code 2
- Error Code 6
- COMPONENTS TESTING
- WIRING DIAGRAMS
- PARTS CATALOG
- Introduction
- 115V Indoor Unit 9-12K
- 230V Indoor Unit 9-12K
- 230V Indoor Unit High Seer 9K
- 230V Indoor Unit High Seer12K
- 230V Indoor Unit 18K
- 230V Indoor Unit 24K
- 230V Indoor Unit 36k
- 115V Outdoor Unit 9K
- 115V Outdoor Unit 12K
- 230V Outdoor Unit 9k
- 230V Outdoor Unit 12k
- 230V Outdoor Unit 18k
- 230V Outdoor Unit 18k
- 230V Outdoor Unit 24k
- Outdoor Unit 36k
- 230v Outdoor Unit 9K HIGH SEER
- 230V Outdoor Unit 12K HIGH SEER
- APPENDIX
- LIMITED WARRANTY
- CUSTOMER SATISFACTION and QUALITY ASSURANCE
- FRIEDRICH AUTHORIZED PARTS DEPOTS
35 PB
INSTALLATION
Power and Wiring
Capacity size Wire Diameter(AWG)
Condenser / Interconnecting Wire
Circuit Breaker Capacity Rating
9k-12k 14 AWG 600V / 14-4 AWG 600V THHN 15A
18k 12 AWG 600V / 14-4 AWG 600V THHN 20A
24-36K 10 AWG 600V / 14-4 AWG 600V THHN 30A
Fig. 435
l Pr and ng
nnng of e Ca
(Inse)
Chis