Service and Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- SPECIFICATIONS
- INSTALLATION
- MAINTENANCE
- R-410A SEALED SYSTEM REPAIR
- TROUBLESHOOTING
- Diagnostic Codes
- Outdoor Unit
- Outdoor Unit When The Compressor Is In Operation
- Indoor Unit
- Led Display
- Test the jumper terminals
- Protection Circuit Fault Isolation
- Compressor Fault Isolation
- Electric FIlter Board Fault Isolation
- Electrical Communication Fault ISOLATION
- Unit does not run
- Error Code 39-DC FAN
- Error Code 39-PG Fan
- Error Code 9
- Error Code 13
- Error Code 8
- Error Code 15
- Error Code 16 Cooling Mode
- Error Code 16 Heating Mode
- Error Code 21 Cooling Mode
- Error Code 11 EEPROM Fault
- Error Code 20
- Error Code 33
- Error Code 34
- Error Code 14
- Error Code 1
- Error Code 2
- Error Code 6
- COMPONENTS TESTING
- WIRING DIAGRAMS
- PARTS CATALOG
- Introduction
- 115V Indoor Unit 9-12K
- 230V Indoor Unit 9-12K
- 230V Indoor Unit High Seer 9K
- 230V Indoor Unit High Seer12K
- 230V Indoor Unit 18K
- 230V Indoor Unit 24K
- 230V Indoor Unit 36k
- 115V Outdoor Unit 9K
- 115V Outdoor Unit 12K
- 230V Outdoor Unit 9k
- 230V Outdoor Unit 12k
- 230V Outdoor Unit 18k
- 230V Outdoor Unit 18k
- 230V Outdoor Unit 24k
- Outdoor Unit 36k
- 230v Outdoor Unit 9K HIGH SEER
- 230V Outdoor Unit 12K HIGH SEER
- APPENDIX
- LIMITED WARRANTY
- CUSTOMER SATISFACTION and QUALITY ASSURANCE
- FRIEDRICH AUTHORIZED PARTS DEPOTS
47 PB
TROUBLESHOOTING
Diagnostic Codes
Outdoor Unit When The Compressor Is In Operation
THE FLASH IS 1 SECOND
No. LED1 LED2 LED3 Reasons for the current operating frequency of
the compressor is limited
1 BLINK BLINK BLINK Normal frequency rising and decreasing, no
limitation
2 OFF OFF ON Frequency decreasing or prohibition of
frequency rising caused by over-current
3 OFF ON ON Frequency decreasing or prohibition of
frequency rising caused by anti-freezing of
refrigeration or anti-overload in heating
4 ON OFF ON Frequency decreasing or prohibition
of frequency rising caused by too high
compressor discharge temperature
5 Limit to the max operating frequency caused
by too low power voltage
6 ON ON ON Operation at xed frequency (in the case of
capability measuring or compulsory operation
at xed frequency)
7 BLINK OFF OFF Protective frequency decreasing against
outdoor overload (overpower, over frequency
conversion rate, over torque, detection of DC
under-voltage)
8 ON OFF OFF Frequency decreasing caused by indoor and
outdoor communication fault
9 OFF ON BLINK Frequency decreasing or prohibition of
frequency rising protection against overload of
outdoor coiled pipe
10 OFF ON OFF Frequency decreasing or prohibition of
frequency rising for power-saving when it
is being used simultaneously with other
appliances