PERFORMANCE RATINGS Multi Zone Cassette - Heat Pumps
9k 12k 18k 24k
INDOOR MODEL
FPHFC09A3A
FPHFC09A3B Wi-Fi
FPHFC12A3A
FPHFC12A3B Wi-Fi
FPHFC18A3A
FPHFC18A3B Wi-Fi
FPHFC24A3A
FPHFC24A3B Wi-Fi
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 9000 12000 18000 24000
CAPACITY HEATING (RATED) Btu 10200 13500 20400 27000
MOISTURE REMOVAL Pts/h 1.9 2.5 3.2 5.0
AIRFLOW (HIGH) CFM 306 471 559 1100
SOUND RATING (MAX.-MIN.) dB-A 40/28 40/28 40/28 40/28
ELECTRICAL DATA
POWER SOURCE V-Hz-Phase 230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-1
POWER AND COMMUNICATION CABLE No. x AWG 4 x 14AWG 4 x 14AWG 4 x 14AWG 4 x 14AWG
REFRIGERATION SYSTEM
CONNECTIONS Flare Flare Flare Flare
LIQUID LINE O.D. in
1
/4
1
/4
1
/4
3
/8
SUCTION LINE O.D. in
3
/8
3
/8
1
/2
5
/8
DIMENSIONS & WEIGHT
W X H X D in 22
1
/2 x 8
1
/2 x 22 33 x 9
3
/4 x 33
NET WEIGHT lbs 31.9 34 61.8 59.5
SHIPPING WEIGHT lbs 38.5 40.7 81.6 79.5
PACKAGE DIMENSIONS W X H X D in 28
3
/4 x 11
1
/2 x 26 39
1
/4 x 37 x 14 39
1
/4 x 37 x 14
1
/2
PERFORMANCE RATINGS Multi Outdoor
18k
24k 36k
OUTDOOR MODEL
FPHMR18A3A
FPHMR24A3A FPHMR36A3A
SPECIFICATIONS
POWER SOURCE
208~230/60/1 208~230/60/1 208~230/60/1
EST. YEARLY OPERATING COST
$ $90 $172 $259
RUNNING CURRENT COOLING RATED
A
6.5
8.7 11
RUNNING CURRENT HEATING RATED
A
7.3
8.7 13
POWER INPUT COOLING MIN. RATED MAX.
W 1440 (510
~
2610) 1920 (420
~
2640)
2520 (700~5000)
POWER INPUT HEATING MIN. RATED MAX.
W 1530 (450
~
3510) 1920 (420
~
4020)
3060 (600~6000)
POWER AND COMMUNICATION CABLE
No. x AWG
4 x 14AWG 4 x 14AWG 4 x 14AWG
DIMENSIONS W x H x D
in
33
7
/8 x 26
3
/8 x 12
1
/4 37
3
/8 x 33 x 13
3
/8
37
3
/8 x 41
3
/8 x 13
3
/8
NET WEIGHT
lbs 108 159 186
SHIPPING WEIGHT
lbs 119 170 216
REFRIGERATION SYSTEM
REFRIGERANT
R410A R410A R410A
FACTORY PRECHARGE
oz
63 81.13 105.82
FACTORY PRECHARGE
ft
49
74 98
LIQUID LINE O.D.
in
1
/4
1
/4
1
/4
SUCTION LINE O.D.
in
3
/8
3
/8
3
/8
MIN./MAX. LINE LENGTH (EACH)
ft
82
66 66
MIN./MAX. LINE LENGTH (TOTAL)
ft
164
197 197
MAX. HEIGHT DIFFERENCE
ft
49
49 49
SOUND PRESSURE LEVEL COOLING
A
55
59 59
SOUND PRESSURE LEVEL HEATING
A
55
59 59
OPERATING RANGE COOLING
°F DB
14
~
115
14~115 14~115
OPERATING RANGE HEATING
°F WB -13~75 -13~75 -13~75
MINIMUM AMPACITY
A
21A
25A 32A
MAX. TD FUSE/ BREAKER
A
30A
30A 50A