SPECIFICATIONS
Product Specications 18K, 24k and 36k Outdoor Condensor
Multi‑Zone Flex 2 Indoor units 2 or 3 indoor units 2 to 4 indoor units 2 to 5 indoor units
Model Name FPHMR18A3A FPHMR24A3A FPHMR36A3A FPHMR42A3A
Gas R410A R410A R410A R410A
Capacity Cooling
Capacity
95
ºF
Btu/h 18000 24000 32000 42000
Heating Rated
Capacity
47
ºF
Btu/h 18000 24000 36000 42000
17
ºF
Btu/h 12200 15400 22800 24000
Heating
Maximum
Capacity
17
ºF
Btu/h 20000 26000 40000 40000
5 ºF Btu/h 18000 24000 36000 36000
Cooling 95
ºF
kW / / / /
Btu/h 18000(7500~24000) 24000(8000~30200) 32000(12000~42000) "42000
(9000~50000)"
Heating 47
ºF
kW / / / /
Btu/h 18000(5800~28700) 24000(5200~37000) 36000(8000~52000) 42000 (9000~52000)
Air ow CFM 3150 4000 5000 5800
m3/h 1850 2353 2941 3411
EER Btu/W•h 12.5 12.5 12.5 10.5
COP Btu/W•w 3 45 3 66 3 37 3.17
COP Btu/ W•h 11 77 12 49 11 50
10 82
SEER Btu/W•h 22 22 21 20
HSPF Btu/W•h 11.0 11 11 10.0
Noise Level dB(A)
(Max)
55 59 59 63
Operating
Range
Cooling °F 14~114.8 14~114.8 14~114.8 14~114 8
°C -10~46 -10~46 -10~46 -10~46
Heating °F ‑13~75.2 ‑13~75.2 ‑13~75.2 -4~75 2
°C -25~24 -25~24 -25~24 -20~24
Compressor
model
Model EATF200D22UMT EATF250D22UMT EATF400D42UMT EATF400D42UMT
Brand GMCC GMCC GMCC GMCC
Electrical Data
Power V/Hz/ph 208~230/60/1 208~230/60/1 208~230/60/1
208~230/60/1
Power input Cooling 95
ºF
W (Rated
Range)
1440(510~2610) 1920 (420~2640) 2520(700~5000) 4060(660~5550)
Heating 47
ºF
W Rated
Range)
1530(450~3510) 1920 (420~4020) 3060(600~6000) 3690(530~6450)
1. Test conditions
Cooling : Indoor: DB80 °C/ WB 67ºF Outdoor: DB95 °C/ WB75°F
Heating: Indoor: DB70 °C/ WB 60ºF Outdoor: DB47 °C/ WB 43 °F
2. The Sound Pressure Level is based on the following conditions:
Outdoor unit:
Measure the noise value of 3 points, the points are 3’(ft) in front of the three sides of the unit surface.
(front/left/right)and height =1/2(unit height +3) ft from oor level, and calculate the weighted average of the noise.
3. The above data was measured in an anechoic chamber. Please take into consideration reected sound of your specic
application environment.
4. All specications are subjected to change by the manufacturer without prior notice.