Spec Sheet

17
PRO SERIES SPECIFICATIONS
PERFORMANCE RATINGS Single Zone - The Insider
®
Concealed Ducted Heat Pumps
SYSTEM MODEL NO.
FPHD093 FPHD123 FPHD183 FPHD243 FPHD363
INDOOR MODEL
FPHFD09A3A FPHFD12A3A FPHFD18A3A FPHFD24A3A FPHSD36A3A
OUTDOOR MODEL
FPHFR09A3A FPHFR12A3A FPHFR18A3A FPHFR24A3A FPHFR36A3A
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu
9000 12000 18000 24000 36000
CAPACITY COOLING (MIN~MAX) Btu
4850-11600 5800-13100 4200-21000 8600-25200 12500-37300
CAPACITY HEATING
@
47
0
F (RATED) Btu
9000 12000 18000 28000 36000
CAPACITY HEATING
@
17
0
F (RATED) Btu
6000 6600 11000 19600 26000
CAPACITY HEATING (MIN~MAX) Btu
4340-12280 4400-14400 5600-24000 7600-28400 15000-39800
SENSIBLE HEAT RATIO
76% 76% 76% 76% 76%
SEER
17.0 19.0 19.0 18.0 18.0
EER
12.0 11.0 12.2 10.48 10.91
COP (@47°F) .
3.2 3.2 3.3 3.61 3.01
HSPF
10.00 10.00 10.00 11.00 9.50
ENERGY STAR
MOISTURE REMOVAL Pts/h
2.0 3.0 5.0 1.9 7.61
AIRFLOW (LOW, MED, HIGH ) CFM
309/259/208 324/285/235 529/441/371 706/588/500 883/735/617
SOUND RATING - INDOOR H/M/L dB(A)
35/33/32 36/34/33 38/37/36 42/38/36 43/40/38
SOUND RATING - OUTDOOR dB(A)
52 54 68 54 61
OPERATING RANGE (COOLING) °F
5-118 5-118 5-118 5-118 5-118
OPERATING RANGE (HEATING) °F
-4-75 -4-75 -4-75 -4-75 -4-75
EST. YEARLY OPERATING COST $
63 83 122 176 376
ELECTRICAL DATA
POWER SOURCE
230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-1
MINIMUM AMPACITY A
23.0 23.0 23.0 23.0 21.0
COOLING WATTS W
750 1091 1670 2200 3300
COOLING AMPS
3.7 4.8 7.6 10.3 14.35
HEATING AMPS
3.2 4.8 7.3 8.7 15.2
MAX. TD FUSE/BREAKER A
15 20 20 35 45
POWER AND COMMUNICATION CABLE No. x AWG
4 x 14AWG 4 x 14AWG 4 x 14AWG 4 x 14AWG 4 x 14AWG
REFRIGERATION SYSTEM
REFRIGERANT
R410a R410a R410a R410a R410a
COMPRESSOR TYPE
Rotary Rotary Rotary Rotary Rotary
CONNECTIONS
Flare Flare Flare Flare Flare
LIQUID LINE O.D. in
1/4 1/4 1/4 3/8 3/8
SUCTION LINE O.D. in
3/8 3/8 1/2 5/8 3/4
FACTORY PRECHARGE ft
25 25 25 25 25
REFRIGERANT CHARGE oz
33.5 45.9 56.5 75.0 111
MIN./MAX. LINE LENGTH ft
10-82 10-82 10-98 10-164 10-164
MAX. HEIGHT DIFFERENCE ft
33 49 49 98 98
DIMENSIONS & WEIGHT
INDOOR UNIT
W X H X D in
35 7/8 x 7 1/2 x 17 5/8 35 7/8 x 7 1/2 x 17 5/8 46 1/2 x 7 1/2 x 17 5/8 35 3/8 x 10 5/8 x 28 3/8 51 1/8 x 13 3/4 x 31 1/2
NET WEIGHT lbs
39.7 39.7 49.6 66.1 112.4
SHIPPING WEIGHT lbs
46.3 46.3 57.3 77.2 132.3
OUTDOOR UNIT
W X H X D in
37 x 25 x 16 1/2 37 x 25 x 16 1/2 39 x 17 3/4 x 28 3/4 43 x 36 1/4 x 18 1/8 43 x 36 1/4 x 18 1/8
NET WEIGHT lbs
75 75 108 155 192
SHIPPING WEIGHT lbs
85 82 117 166 215
TOTAL NET WEIGHT lbs
107 108 108 214.5 262.5
TOTAL SHIPPING WEIGHT lbs
123.5 121 158 245.5 305.4
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .12 per kWh.
For more information, visit www.ftc.gov/energy.
Due to continuing research in new energy-saving technology, specications are subject to change without notice.