Submittal (2020)

ACCESSORIES
*Insulated line sets are available for all Friedrich split systems in 15 ft. and 35 ft. lengths. Each line set is equipped with are nuts on both ends.
Both liquid and suction lines are insulated. Line sets can be joined together with eld supplied double male connectors.
Each system requires one line set for each indoor unit installed.
TORQUE WRENCH SETTINGS
Outside Diameter Torque
mm inch ft-lbs. N·m
6.35
1
/4
13 18 17.6 24.5
9.52
3
/8
25 30 33.3 41.2
12.7
1
/2
40 47 53.9 64.7
15.88
5
/8
45 59 61.7 80.4
REFRIGERATION LINE SETS (REQUIRED)
OUTSIDE DIMENSIONS
Floating Air
®
Pro Multizone Outdoor
SYSTEM MODEL
Liquid Suction 15’ Lineset Kit 35’ Lineset Kit
FPHMR18A3A 1/4 3/8 T32150 T32350
FPHMR24A3A 1/4 3/8 T32150 T32350
FPHMR36A3A 1/4 3/8 T32150 T32350
REFRIGERATION LINE SETS
MIN./MAX. LENGTHS
Floating Air
®
Pro Outdoor
SYSTEM MODEL
Min. (ft.) Max. Each/Total (ft.)
Floating Air
®
Pro Multi Zone Outdoor
FPHMR18A3A 25 82/164
FPHMR24A3A 25 66/197
FPHMR36A3A 25 66/246
WALL CONTROLLER
FPWC1 Optional wired wall controller
Floating Air
®
Pro Ceiling Cassette Multi Zone Submittal 2020