Overcharged Refrigerant Systems
Compressor amps will be near normal or higher. 
Noncondensables can also cause these symptoms. 
To conrm, remove some of the charge, if conditions 
improve, system may be overcharged. If conditions 
don’t improve, Noncondensables are indicated. 
Whenever an overcharged system is indicated, always 
make sure that the problem is not caused by air ow 
problems. Improper air ow over the evaporator coil 
may indicate some of the same symptoms as an over 
charged system. 
An overcharge can cause the compressor to fail, since 
it would be “slugged” with liquid refrigerant. 
The charge for any system is critical. When the 
compressor is noisy, suspect an overcharge, when you 
are sure that the air quantity over the evaporator coil is 
correct. Icing of the evaporator will not be encountered 
because the refrigerant will boil later if at all. Gauges 
connected to system will usually have higher head 
pressure (depending upon amount of over charge). 
Suction pressure should be slightly higher.
Figure 602 (Overcharged System)
WARNING
HIGH PRESSURE HAZARD 
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure to follow these procedures could 
result in serious injury or death. 
WARNING
RISK OF ELECTRIC SHOCK 
Unplug and/or disconnect all electrical power 
to the unit before performing inspections, 
maintenances or service. 
Failure to do so could result in electric shock, 
serious injury or death.
R-410A SEALED SYSTEM REPAIRS