Service & Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
48 PB
COMPRESSOR CHECKS
WARNING
ELECTRIC SHOCK HAZARD 
Turn  off  electric  power  before  service  or 
installation.  Extreme  care  must  be  used,  if  it 
becomes necessary to work on equipment with 
power applied.
Failure to do so could result in serious injury or 
death.
Single Phase Resistance Test 
Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1). 
Touch the leads of the ohmmeter from terminals common to start (“C” to “S”). Next, touch the leads of the ohmmeter from 
terminals common to run (“C” to “R”).
Add values “C” to “S” and “C” to “R” together and check resistance from start to run terminals (“S” to “R”). Resistance “S” to 
“R” should equal the total of “C” to “S” and “C” to “R.” 
In a single phase PSC compressor motor, the highest value will be from the start to the run connections (“S” to “R”). The next 
highest resistance is from the start to the common connections (“S” to “C”). The lowest resistance is from the run to common. 
(“C” to “R”) Before replacing a compressor, check to be sure it is defective. 
GROUND TEST 
Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good connection 
is a must) and the other probe in turn to each compressor terminal. If a reading is obtained the compressor is grounded and 
must be replaced.
Check the complete electrical system to the compressor and compressor internal electrical system, check to be certain that 
compressor is not out on internal overload. 
Complete evaluation of the system must be made whenever you suspect the compressor is defective. If the compressor has 
been operating for sometime, a careful examination must be made to determine why the compressor failed. 
Many compressor failures are caused by the following conditions:
  1.Improper air ow over the evaporator.
  2.Overcharged refrigerant system causing liquid to be returned to the 
compressor.
  3.Restricted refrigerant system.
  4.Lack of lubrication.
  5.Liquid refrigerant returning to compressor causing oil to be washed out of 
bearings.
  6.Noncondensables such as air and moisture in the system. Moisture is 
extremely destructive to a refrigerant system.
  7.Capacitor.
CHECKING COMPRESSOR EFFICIENCY 
The reason for compressor inefciency is normally due to broken or damaged suction and/or discharge valves, reducing the 
ability of the compressor to pump refrigerant gas.
This condition can be checked as follows:
  1. Install a piercing valve on the suction and discharge or liquid process tube.
  2. Attach gauges to the high and low sides of the system.-
  3. Start the system and run a “cooling or heating perfor mance test.” If test shows:
    A. Below normal high side pressure
    B. Above normal low side pressure
    C. Low temperature difference across coil 
  The compressor valves are faulty - replace the compressor.
WARNING
HIGH PRESSURE HAZARD 
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure to follow these procedures could 
result in serious injury or death. 
Figure 701 (Resistance Chart)